14
16. BstEV: xxxxx
▼
17. BstTM: xxxx.xH
18. C1:Off C2:Off
19. C3:Off C4:Off
The total time duration the unit has been in boost mode
since the latest reset.
The status of the dry contact C1 and C2.
The status of the dry contact C3 and C4.
Page 6
20. C5:On C6:On
21.
MainFW
: xx.xx
22.
LCDFW
: xx.xx
23. HW : xx.xx
▲
The status of the dry contact C5 and C6.
The firmware version of Main CPU in UPS.
The firmware version of LCD panel in UPS.
The hardware version of UPS.
3.2
Event Menu
User can view the active event log and history event log via this menu. After pressing ESC button in Event page,
it will return to default page.
Event Log Page
Explanation
► 1. Active Log
2. History Log
Active event log enquiry.
History event log enquiry and clear. Maximum log number is 200.
Active Log Page
Explanation
yy-mm-dd hh:mm
Over Load
In xxxxxx Mode
xx/xx
▼
Date and time when this event occur
Event type
UPS operation mode when this event occurs
Viewing event index/Total active event number
3.3
Setting Menu
User can set various critical parameters in this menu. Choose the desired function on the screen by pressing
ENTER button. Press ESC button to return to default page. (To enter in Setting menu use default password:
11111)
Setting page
Explanation
► Dry Contact ▼
Input Contact
AVR Feature
Line Qualify
Dry Contact:
It indicates programmed values of C1-C6 contacts.
Factory default settings: C1, C2=On battery; C3, C4=battery low; C5,
C6=Timer.
Illustrations for each programmed value as below.
-
On battery: Energized when Unit in INV mode.
-
Battery low: Energized when the battery voltage is lower than the
configurable battery low voltage. The default value is 46VDC.
-
Timer: Energized after the unit has been in INV mode for the setting
backup time. The factory default value is 2 hours.
-
Alarm: Energized when any alarm occurs in UPS.
-
Fault: Energized when any fault occurs in UPS.
-
Off: Energized while the UPS is off.
-
Disable: The dry contacts become invalid.
Input Contact:
It indicates selectable options for input contacts.
Factory default setting is
“
Ext Fan Failed
”
.
Selectable options are listed as below.
-
User program
-
Ext Alarm
-
Ext Battery Alarm