16
3.4
Control Menu
Press SCROLL button to switch desired option in Control menu and press ENTER button to confirm new option.
Pressing ESC button will return to default page. (To enter in Setting menu use default password: 11111)
Control page
Explanation
Self Test:
⊙
Start
○
Stop
Starts the Self-Test.
CAUTION:
The unit must be in Normal, Boost or Buck Mode before starting
the self-test.
Dry Test:
⊙
On
○
Off
○
Cancel
Starts the dry contact test.
-
On: All dry contacts are energized. This action will be finished
automatically after 1 minute.
-
Off: All dry contacts are ineffective. This action will be finished
automatically after 1 minute.
-
Cancel: Cancel this test immediately.
Ext Fan Test:
⊙
On
○
Off
○
Cancel
Starts the external fan test.
-
On: The external fan has power from battery. This action will be finished
automatically after 1 minute.
-
Off: Cut off battery power. This action will be finished automatically after
1 minute.
-
Cancel: Cancel this test.
UPS Output:
⊙
On
○
Off
UPS output can be turned ON or OFF. This option is available when the UPS is
in INV, Boost, Buck or Normal Mode.
Reset Event/TM?
⊙
Yes
○
No
It resets all event numbers and time duration to zero.
3.5
Help Menu
It shows UPS model name in Help menu.
Help page
Explanation
Indicates UPS model name.
UPS-2000A