background image

  Sirius 250 Handbook                                                                                                                                                                                                                                   Part Number 17132

Input Parameters

NOMINAL INPUT VOLTAGE RANGE

94.5 - 240VAC or 133-330VDC

MAX. INPUT VOLTAGE RANGE

85-264VAC or 120-360VDC

INPUT FREQUENCY

47-63Hz

MAXIMUM INPUT CURRENT

5A AC or 3.4A DC

INRUSH CURRENT

<50 AMPS

Output Parameters

Adjustment and Derating.

The Sirius 250 series is designed to provide a max output power of 250W at 
nominal output voltages.  The following procedure must be used to ensure the 
PSU is operated within its ratings:

Calculate user power for each module (volts x amps).

Add all the individual module powers together.  The total power must not    

 

exceed the value given in the following tables.

Calculate secondary transformer turns x amps for each module.  (See  

 

 

outputs table for transformer secondary turns).

Add all the module turns x amps together and this must not exceed 75AT.

If necessary reduce the loading until the conditions are met, ie. power and   

 ampere-turns 

maxima.

OUTPUTS

Cooling,Output Power and Output Current  Limitations
i) Power limitation method.

Integral Fan Cooling (all orientations)

Normal Airfl ow

(air into unit at input end)

Reverse Airfl ow

(air into unit at output 

end)

Top Fan with Molex 

(TM)

End Fan with Molex 

(EM)

End Fan with IEC

 (EI & EIF)

End Fan with IEC

(EIR & EIFR)

245W

250W

250W

210W

To determine the component temperatures tests must be conducted in accord-
ance with the requirements of IEC/EN/UL/CSA60950-1, Clause 4.5.  Considera-
tion should also be given to the requirements of other safety standards.  Note:  
Max. temperatures given are as required by EN60950-1 or to provide satisfac-
tory reliability, whichever is the lower.
Test requirements include: PSU to be fi tted in its end-use equipment and oper-
ated under the most adverse conditions permitted in the end-use equipment 
handbook/specifi cation and which will result in the highest 
temperatures in the PSU.  To determine the most adverse conditions consid-
eration should be given to the maximum operating ambient, PSU loading and 
input voltage, ventilation, equipment orientation, the position of doors & covers, 
etc.  Temperatures should be monitored using type K fi ne wire thermocouples 
(secured with cyanoacrylate adhesive, or similar) placed on the hottest part of 
the component and the equipment should be run until all temperatures have 
stabilised.

Customers Airfl ow (all orientations) (NM)

Normal Airfl ow (air into unit at input end)

Reverse Airfl ow (air into unit at output end)

2.5 m/s

3 m/s

2.5 m/s

3 m/s

220W *

230W

175W

200W

Circuit Ref

Description

Max Temp (

0

C)

TX1

Power transformer primary, secondary and core

130

TX2

Drive transformer windings

110

L1 & L6

Choke winding

110

L12

Choke winding and core

120

-

All other choke windings

115

F1

Input fuse end cap and clip

100

C1 & C18

X capacitors

100

C5

Reservoir electrolytic capacitor

85

-

Electrolytic capacitors < 10mm diaameter

90

-

Electrolytic capacitors >- 10mm diameter

95

* Output 2, 3.3V, is derated to 15A from 16A.

ii) Temperature Measurement Method:
The following method must be used for determining the safe operation of PSU’s 
with the LM option (open frame).  It may be used as an alternate method to (i) 
above, for determining the safe operation of NM option PSU’s.
For PSU’s cooled by customer supplied airfl ow the components listed in the 
table below must not exceed the temperatures given (including when the end 
use equipment is operated at its maximum permitted ambient), consequently 
the maximum temperature rise permitted is given by the temperatue given in the 
table minus the T mra (maximum ambient) of the end use environment (maxi-
mum permitted T

 

mra

 

is 50

0

C).  All other ratings given in this handbook remain 

unchanged except that the maximum output power is 250W.  

Module

Output 

Range

Current

Turns

Short Circuit 

Current (*3)

Min setting for 

Hazardous Energy 

(*4)

5/3 base

5.0 - 5.7V

35A(*2)

1T

80A

3V

2.7 - 3.5V

16A

1T

80A

-

5/12 base 5.0 - 5.7V

35A(*2)

1T

80A

3V

11 - 16V

8A (12A peak)

4T

20A

-

5 base

5 - 5.7V

35A(*2)

1T

80A

3V

24 base

23-28V

10A(*2)

4T

20A

12V

A

4.5 - 5.5V

10A

2T

40A

-

B

11 - 15V

8A

4T

20A

-

C

16 - 28V

4A

8T

10A

-

D

4.5 - 5.5V

5A

2T

40A

-

2.7 - 3.9V

5A

2T

40A

-

E

4.5 - 5.5V

5A

2T

40A

-

9 - 15V

4A

4T

20A

-

F

4.5 - 5.5V

5A

2T

40A

-

16 - 28V

2A

7T

11.5A

-

G

9 - 15V

4.5A

4T

20A

-

9 - 15V

4.5A

4T

20A

-

H

9 - 15V

4A

4T

20A

16 - 28V

2A

7T

11.5A

-

J

16 - 28V

2A

7T

11.5A

-

16 - 28V

2A

7T

11.5A

-

L

1.8 - 3.9V

10A

2T

40A

-

M

4.5 - 5.5V

5A

2T

40A

-

4.5 - 5.5V

5A

2T

40A

-

N

11 - 14.5V

8A

4T

20A

-

*2 = A minimum load of 10% is required on these outputs.
*3 = Maximum current if output is short circuited, within 1 minute current limit changes to 

‘hiccup’ mode to give a lower average current.
*4 = It may not be possible to set the output this low.

Output Ratings

See component layout drawing on page 4

Approval Limitations:  Use in North America (AC units only)

When this product is used on 180VAC-250VAC mains with no neutral, connect the two live wires 
to L(live) and N (neutral) terminals on the input connector.  In this instance double pole fusing is 
required.

High Voltage Warning

Dangerous voltages present within the power supply.  Do not remove covers. 

External Hot Surfaces

Section 6 of the Health and Safety at Work Act requires that manufacturers have an obligation to 
protect service engineers as well as users.  In order to comply with this, a label must be fi tted to 
these products which is clearly visible to service personnel accessing the overall equipment, and 
which legibly warns that surfaces of these products may be hot and must not be touched when the 
products are in operation. 

Safety Earthing Screw

On products with an enclosure, special safety earthing screws are used  which connect the cover to 
the chassis. They must not be removed. 

Safety Class of Protection

These products are designed for the following parameters : Material Group IIIb, Pollution Degree 2, 
Overvoltage Category II, Class 1 (earthed), Indoor use as part of an overall  equipment such that 
the product is accessible to service engineers only.   

Energy  and Voltage Hazards

Certain modules are capable of providing hazardous energy (240VA) according to output voltage 
setting.  Final equipment manufacturers must provide protection to service personnel against 
inadvertent contact with these module output terminals.  If set such that hazardous energy can 
occur then the module terminals or connections must not be user accessible.Non-seriesed outputs 
that are earthed in the end use equipment are SELV .If outputs are not earthed they must be 
considered hazardous, as a  single fault in the secondary may make them exceed the SELV limits 
between output and earth. If any output is non-SELV  then all outputs become non SELV. Outputs 
connected in series may produce non-SELV levels, and this must be taken into account in the 
end-use application.

Servicing

These products are not customer serviceable.  Repairs may only be carried out by Lambda UK or 
their authorised agents. These products are not authorised for use as critical components in nuclear 
control systems, life support systems or equipment for use in hazardous environments without the
 express written approval of the Managing Director of Coutant Lambda Ltd.  

Important safety instructions

Reviews: