Activation of Auto-setting function for gas valve calibration
THIS PROCEDURE MUST ONLY BE CARRIED OUT IN THE FOLLOWING CASES: GAS VALVE REPLACEMENT,
CARD REPLACEMENT, CONVERSION FOR GAS CHANGE
.
The B&P Gas Valve (with integrated modulating operator) does not provide for mechanical calibration: the minimum
and maximum power adjustments are therefore electronically done via two parameters:
Gas valve pre-calibration
1.Connect a pressure gauge to monitor the gas valve outlet pressure.
2.Enable the
Auto-setting
function (Parameter b12=1).
3.Activate the calibration procedure by pressing the h button and Eco/Comfort button together for 5 seconds.
The message "Au-to" immediately appears (in two successive flashes) and the burner is lit. Within 8 seconds (nat-
ural gas and LPG) the boiler finds the ignition point. The ignition point, absolute minimum current Offset (Parameter
q01) and absolute maximum current Offset (Parameter q02) values are stored by the card.
Gas valve calibration
1.The display will show "q02" flashing; the modulation current is forced to the pre-calibration value of the absolute max-
imum current Offset parameter (Parameter q02).
2.Press the DHW buttons to adjust the parameter "q02" until the maximum nominal pressure minus 1mbar is reached
on the pressure gauge. Wait 10 seconds for the pressure to stabilise.
3.Press the
DHW “+”
button to set the parameter
“q02”
until the maximum nominal pressure is reached on the pressure
gauge. Wait 10 seconds for the pressure to stabilise.
4.If the pressure read on the pressure gauge is different from the maximum nominal pressure, proceed in increments
of 1 or 2 units of the parameter "q02" by pressing the
DHW “+”
button: after each change, wait 10 seconds for the
pressure to stabilise.
5.When the pressure read on the pressure gauge is equal to the maximum nominal pressure (the newly calibrated value
of the parameter "q02" is automatically saved), press the
heating “–”
button: the display will show "q01" flashing;
the modulation current is forced to the pre-calibration value of the absolute minimum current Offset parameter (Pa-
rameter q01).
6.Press the DHW buttons to adjust the parameter "q01" until the minimum nominal pressure plus 0.5mbar is reached
on the pressure gauge. Wait 10 seconds for the pressure to stabilise.
7.Press the
DHW “-”
button to adjust the parameter "q01" until the minimum nominal pressure is reached on the pres-
sure gauge. Wait 10 seconds for the pressure to stabilise.
8.If the pressure read on the pressure gauge is different from the minimum nominal pressure, proceed in decrements
of 1 or 2 units of the parameter
“q01”
by pressing the
DHW “-”
button: after each change, wait 10 seconds for the
pressure to stabilise.
9.When the pressure read on the pressure gauge is equal to the minimum nominal pressure (the newly calibrated value
of the parameter "q01" is automatically saved.), recheck both adjustments by pressing the heating buttons and cor-
rect them if necessary by repeating the procedure described above.
10.The calibration procedure ends automatically after 15 minutes or by pressing the
heating “+”
and Eco/Comfort but-
tons together for 5 seconds.
Checking of gas pressure values and adjustment with limited range
•Check that the supply pressure complies with that indicated in the technical data table.
•Connect a suitable pressure gauge to the pressure sampling point
“B”
located downstream from the gas valve.
•Activate the
TEST
mode and follow the instructions for checking the gas pressures at maximum power and minimum
power (see next par.).
If the maximum and/or minimum nominal pressures read on the pressure gauge are different from those indicated in
the technical data table, proceed with the next sequence.
•Press the Eco/Comfort button for 2 seconds to go to the gas valve Calibration with limited range mode.
•The card goes to the setting
“q02”
; displaying the currently saved value by pressing the DHW buttons.
•If the
maximum pressure
read on the pressure gauge is different from the nominal one, proceed in increments/dec-
rements of 1 or 2 units of the parameter
“q02”
by pressing the DHW buttons: after each change, the value is stored;
wait 10 seconds for the pressure to stabilise.
•Press the heating “-” button (ref. 3 - fig. 1).
Contents
Description
Natural Gas
Propane Gas
q01
Absolute minimum current offset
0÷100
0÷150
q02
Absolute maximum current offset
0÷100
0-150
Summary of Contents for EASY TECH D C24
Page 8: ...EASY TECH D C24 8 SR cod 3542B950 Rev 00 01 2023 2 8 1 0 bar F37 1 8 300 Fh 0 8 8 1 9 9 2 1 1...
Page 11: ...EASY TECH D C24 11 SR cod 3542B950 Rev 00 01 2023 19 10 2 6 B 72 139 138 3 4...
Page 20: ...EASY TECH D C24 20 SR cod 3542B950 Rev 00 01 2023 3 3 B antirefoleur 14 1 3 5 0 5...
Page 24: ...EASY TECH D C24 24 SR cod 3542B950 Rev 00 01 2023 16 700 709 400 117 100 65 66 66 66 36 101...
Page 92: ...EASY TECH D C24 92 RU cod 3542B950 Rev 00 01 2023 2 8 1 0 F37 1 8 300 Fh 0 8 8 1 9 9 2 1 1...
Page 95: ...EASY TECH D C24 95 RU cod 3542B950 Rev 00 01 2023 19 10 2 6 0 5 B 72 139 138 3 4...
Page 104: ...EASY TECH D C24 104 RU cod 3542B950 Rev 00 01 2023 cap 4 3 3 B 14 1 3 5 0 5...
Page 108: ...EASY TECH D C24 108 RU cod 3542B950 Rev 00 01 2023 16 700 709 400 117 100 65 66 66 66 36 101...
Page 115: ......
Page 116: ...6 7 5...
Page 119: ...6 7 5 27 278 241 11 10 8 9 95 32 56 36 194 42 14 136 74 114 37...
Page 120: ...6 7 5 6 7 78 56 27 126 278 81 22 95 194 42 114 10 8 7 44 74 37 32 145 9 11 14 36...
Page 121: ...6 7 5 700 709 400 117 110 120 81 100 65 66 66 66 36 101...
Page 122: ...6 7 5 6 7 6 7 400 700 330 184 207 39 65 68 69 65 154 131...
Page 123: ...6 7 5 E 3...
Page 124: ...6 7 5 5 6 7 G G E E E...
Page 125: ...6 7 5 3 5 0 5...
Page 126: ...6 7 5 L 5HVHW 5HVHW U FR RPIRUW 5HVHW...
Page 128: ...6 7 5 3 E E E E 3 E E E E 3 E E E E 3 E E E E 3 E E E E 3 3 3 3 2 E E E 2 E 2 E E 3 3 3 6 7...
Page 129: ...6 7 5 5HVHW W6 Q L U W6 Q L 5HVHW U W6 3 E E E E E E E E E E E E 6 7 3 3 3 3 3 3...
Page 130: ...6 7 5 7 67 UHVHW 7 67 E E E E E E E E E E E E E E E E E...
Page 133: ...6 7 5 0 25 1 E 3 T T...
Page 134: ...6 7 5 72 139 138 3 4...
Page 135: ...6 7 5 5 99...
Page 136: ...6 7 5 1 SU D 2...
Page 137: ...6 7 5 K 2 1 1...
Page 139: ...6 7 5 20 257 2 RII 2 20 257 RII UHVHW 8...
Page 140: ...6 7 5 G G G RII RII...
Page 141: ...6 7 5 6 7 FRQRP G G 3 G 1 7 2 16 3 6 5 11 15 10 12 4 14 13 9 8...
Page 142: ...6 7...
Page 143: ...6 7 5 8 0 8 70 7 4 2 36 0 71 0 EU 19 2012...
Page 144: ...6 7...