TECHNICAL DATA
Model
G 1300
G 2000
Type
Two-stage progressive or modulating
Functioning
Intermittent
Regulation
Air/gas proportional valve
Maximum heat output
KW
1296
1918
Minimum heat output
KW
237
336
NO
x
class
-
2
2
Gas category
-
G20 / G30-G31
Maximum gas flow rate (15°C - 1013.5 mbar)-natural gas
m
3
/h
136,5
202
Minimum gas flow rate (15°C - 1013.5 mbar)-natural gas
m
3
/h
25
36,5
Electric protection rating
IP
20
20
Motor electric power supply (three phase)
V / Hz
400 / 50-60
*
400 / 50-60
*
Auxiliary electric power supply (single phase)
V / Hz
230 / 50
230 / 50
Max. absorbed power
W
2200
3000
Transformer (voltage/secondary current)
KV / mA
15 / 48
15 / 48
Functioning temperature (min/max)
°C
0 / 40
0 / 40
Noise
dbA
85
86
Weight of the burner body (without ramp)
Kg
45
48
U
M
0,00
1,00
2,00
3,00
4,00
5,00
6,00
7,00
8,00
mbar
0
200
400
600
800
1000 1200 1400 1600 2000 2200
kW
*
It is possible the 60 Hz power supply only with suitable electric motor.
WORK CURVES
Reference parameters for choosing blown air gas burners.
Blown air gas burners can be installed on both pressurised and vacuum boilers. It is essential to always refer to
the flow-pressure working curve as burner flow (expressed in kW) remains strongly linked to the pressure present
in the combustion chamber.
U
M
Example:
Boiler: power to hearth = 1400 kW and
pressure in combustion chamber = 3.0
mbar.
The meeting point between the straight
lines of combustion chamber pressure
and power to the hearth must fall within
the operating range of the boiler (see
example image).
Pressure in the combustion chamber
Flow rate to the boiler furnace