background image

Taura 24 MCS W TOP

22

1.3 Turning on and off

Ignition

•  Open the gas valve ahead of the boiler.
•  Supply the unit with electricity.
  Turn the selector 3 onto 

 (winter) or onto 

 (summer) 

•  Turn the heating and hot water knob onto the required temperatures. 
•  The boiler is ready to function automatically whenever hot water is drawn or the room thermostat calls for heat-

ing.

If after the ignition cycle the burners fail to ignite and the red LED comes on, turn the selector onto RESET 
for 1 second and then back onto 

 or onto 

. The controller will repeat the ignition cycle in the next 30 

seconds. If the burners fail to ignite even after the third attempt, refer to chap. 3.1.

In case of an electrical power failure while the boiler is working, the burners will go out and re-ignite auto-
matically when power is restored.

Turning off

Turn the selector onto 0.

When the boiler is turned off, the electronic card is still powered.
Hot water and heating operation are disabled, all the LEDs are off; but the antifreeze function stays on

The antifreeze system will not work if the electricity and/or gas supply to the unit are cut off.
To avoid damage caused by freezing during long shutdowns in winter, it is advisable to drain all water from 
the boiler, the tap water and the system water; or drain off just the tap water and add a suitable antifreeze 
to the heating system, as prescribed in chap. 2.3.

1.4 Adjustments

Water system pressure adjustment

The filling pressure with the system cold, read on the boiler water gauge, must be about 1.0 - 1.5 bar. If the system 
pressure falls to values below the minimum, bring it back to the initial value by operating the filling cock (see fig. 7 
part 74). At the end of the operation always close the filling cock.

2. INSTALLATION

2.1 General Instructions

BOILER INSTALLATION MUST ONLY BE PERFORMED BY QUALIFIED PERSONNEL, IN ACCORDANCE WITH ALL 
THE INSTRUCTIONS GIVEN IN THIS TECHNICAL MANUAL, THE PROVISIONS OF CURRENT LAW, THE PRESCRIP-
TIONS OF NATIONAL AND LOCAL STANDARDS AND THE RULES OF PROPER WORKMANSHIP.

2.2 Place of installation

The unit’s combustion circuit is sealed off from the installation room and therefore the unit can be installed in any 
kind of room. However, the installation room must be sufficiently well ventilated to prevent any dangerous condi-
tions from forming in the event of even slight gas leakage. This safety standard is required by the EEC Directive no. 
90/396 for all gas units, including those with a so-called sealed chamber.
Therefore the place of installation must be free of dust, flammable materials or objects or corrosive gases. The room 
must be dry and not subject to freezing.
The boiler is fitted to be installed on a wall and is equipped as standard with a set of brackets. The LEJ LINE plumbing 
kits also include a paper template to mark the drilling points on the wall if these kits are used. Secure the bracket to 
the wall and hook on the boiler.  The wall fixing must ensure a stable and effective support for the generator.

Summary of Contents for Taura 24 MCS W TOP

Page 1: ...DE GAS CON C MARA ESTANCA PARA AGUA SANITARIA Y CALEFACCI N CALDEIRA MURAL A G S C MARA ESTANQUE PARA PRODU O DE GUA QUENTE SANIT RIA E AQUECIMENTO cod 3540D95 0 ediz 06 2006 AZIENDA CERTIFICATA ISO 9...

Page 2: ...nit breaks down and or functions poorly deactivate it do not make any attempt to repair it or directly intervene Contact profession ally qualified personnel Any repair replacement of products must onl...

Page 3: ...iency heat generator for heating and hot water production running on natural or liquefied petroleum gas equipped with an open flue burner with electronic ignition airtight chamber with forced ventilat...

Page 4: ...s Water system pressure adjustment The filling pressure with the system cold read on the boiler water gauge must be about 1 0 1 5 bar If the system pressure falls to values below the minimum bring it...

Page 5: ...y under these conditions it is advisable to refill it with treated water Antifreeze system antifreeze fluids additives and inhibitors The boiler is equipped with an antifreeze system that turns on the...

Page 6: ...city line The connections to the grid must be made with a permanent connection and equipped with a bipolar switch whose contacts have a minimum opening of at least 3 mm interposing fuses of max 3A bet...

Page 7: ...for coaxial pipes Insert the diaphragm on the aluminium section 60 of the upper flange of the boiler Diaphragm for separate pipes Insert the diaphragm under the flanged air inlet section 80 84 Connec...

Page 8: ...tion protection air end piece 80 2 Rooftop outlet 80 125 TEE reduction for separate ducts 12 Caution use solely Lamborghini Caloreclima fume suction outlet kits Air suction 80 Air diaphragm Air Fumes...

Page 9: ...ct WINTER yellow LED on select RESET for 5 seconds LEDs blinking fast for two seconds select WINTER turn the hot water knob ref 2 fig 1 onto minimum for Natural Gas operation or onto maximum for LPG o...

Page 10: ...00 100 2 Gas type selection 0 Natural gas 1 LPG 0 Natural gas 3 Lighting Power 0 60 50 4 Heating idle time 0 0minutes 1 2 5 minutes 1 2 5 minutes 5 Heating pump Post Circulation 0 0minutes 1 2 5 minut...

Page 11: ...onds turn to Winter when the 3 LEDs blink fast Selector turned to Reset for 5 seconds turn to Winter when the 3 LEDs blink fast Selector turned to Reset for 5 seconds turn to Winter when the 3 LEDs bl...

Page 12: ...OFF OFF Natural gas ON BL OFF OFF LPG Red Green Yellow Lighting power OFF OFF OFF 00 06 ON BL OFF OFF 06 13 OFF OFF ON BL 13 21 ON BL OFF ON BL 21 29 OFF ON BL OFF 29 36 ON BL ON BL OFF 36 44 OFF ON B...

Page 13: ...ated on the meter corresponds to that given in the technical data table in chap 4 Make sure that with no call for heating the burner correctly ignites on opening a hot water tap Check that during heat...

Page 14: ...hot water temperature to maximum 4 Wait 10 15 minutes for the boiler to stabilize 5 Take the measurement Analyses made with an unstabilized boiler can cause measurement errors Air Fumes Fig 5 Opening...

Page 15: ...Tap water sensor fault Fault Possible cause Cure Green Yellow Red Heating sensor damaged No circulation of water in the system Air in the system Check the gas flow to the boiler is regular Check the w...

Page 16: ...ig 6 Top view Bottom view Key 1 Heating system delivery 3 4 2 Hot water outlet 1 2 3 Gas inlet 1 2 4 Tap water inlet 1 2 5 Heating system return 3 4 If using the LEJ LINE plumbing kit the distances fo...

Page 17: ...amber 20 Burner assembly 21 Main nozzle 22 Burner 26 Combustion chamber insulation 27 Copper exchanger for heating and hot water 28 Fume manifold 29 Fume outlet manifold 32 Heating circulator 34 Heati...

Page 18: ...nozzles G31 mm 11x0 79 LPG supply pressure G31 mbar 37 0 Pressure at LPG burner G31 mbar 35 0 5 0 LPG delivery G31 kg h 2 00 0 65 Heating Maximum working temperature in heating C 90 Maximum working p...

Page 19: ...FUSE CAUTION Before connecting the room thermostat or the remote timer control remove the jumper on the terminal block Fig 8 Key 16 Fan 32 Heating circulator 34 Heating temp sensor 38 Flow switch 42...

Page 20: ...per l evoluzione del prodotto The illustrations and data given are indicative and are not binding on the manufacturer LAMBORGHINI reserves the right to make those changes considered necessary for the...

Reviews: