Connection with separate pipes
Remove the air inlet closing cap. Fit the two flanged sections Ø80, with their seals. If necessary, install the diaphragm
under the air inlet section
Losses eq
m
Component
Drawing
Suction
Outlet
Vertical
Outlet
Horizontal
Accessories Ø 80
Pipe Ø 80 male-female
1
1
2
Bend 45° Ø80
1,2
2,2
Bend 90° Ø80 male-female
1,5
2,5
Condensate collection cup coupling
/
3
/
Windproof end piece for products of combustion Ø 80 mm
/
/
5
Suction protection air end piece Ø 80
2
/
/
Rooftop outlet 80/125 + TEE reduction for separate ducts
/
12
Caution:
use solely Lamborghini Caloreclima fume suction/outlet kits
** Air suction Ø 80
Air diaphragm
Air
Fumes
Remove
the plug
Connection with separate pipes
1. Completely define the layout of the system of split flues, including accessories and outlet end pieces.
2. Refer to the following table and identify the losses in
eq
m of each component according to the position of
installation.
3. Check that the total sum of the losses is less than or equal to the maximum permissible value:
35
eq
m.
Table of pipe and accessory losses
Taura 24 MCS W TOP
26