AXE 3 D UNIT 32 R HR
15
EN
cod. 3541B310 - 10/2011 (Rev. 00)
Service Menu
The card is equipped with two Menus: one for configuration and the other defined Serv-
ice.
The configuration Menu is accessed by pressing the DHW buttons together for 10 sec-
onds. Only one parameter modifiable only from card for security reasons is available.
To exit the configuration Menu, press the DHW buttons together for 10 seconds.
The card Service Menu is accessed by pressing the Reset button for 10 seconds. Press
the Heating buttons to select "tS", "In", "Hi" or "rE". "tS" means Transparent Parameters
Menu, "In" Information Menu, "Hi" History Menu, and "rE" History Menu Reset. After se-
lecting the Menu, press the Reset button to access it.
"tS" - Transparent Parameters Menu
The card is equipped with 20 transparent parameters also modifiable from Remote Con-
trol (Service Menu):
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to modify the value of a parameter: the change will be au-
tomatically saved.
Press the Reset button to return to the Service Menu. Press the Reset button for 10 sec-
onds to exit to the card Service Menu.
"In" - Information Menu
The card can display the following information:
Press the Heating buttons to scroll the list of information. In case of damaged sensor, the
card displays hyphens.
Press the Reset button to return to the Service Menu. Press the Reset button for 10 sec-
onds to exit to the card Service Menu.
Remote
Control
Card
Description
Transparent Parameters
Range
Default
NO
P01
External or internal flame control selection
0=External, 1=Internal 0=External
Remote
Control
Card
Description
Transparent Parameters
Range
Default
01
P01
System water pressure protection
selection
0=Pressure switch,
1=Pressure transducer
1=Pressure transducer
02
P02
Boiler type selection
1=Heating only
2=Storage with probe
3=Storage with thermostat
4=Instantaneous
5=Bithermal instant.
6=Storage with probe
1
03
P03
Heating pump activation temperature
(P02=1)
0-80°C
30°C
Heating pump activation temperature
(P02=2)
0-80°C
30°C
Heating pump activation temperature
(P02=3)
0-80°C
30°C
Heating pump activation temperature
(P02=4)
0-80°C
30°C
Heating pump activation temperature
(P02=5)
0-80°C
30°C
Heating pump activation temperature
(P02=6)
0-80°C
30°C
04
P04
Heating pump Post-Circulation
0-20 minutes
6 minutes
05
P05
Heating standby time
0-10 minutes
2 minutes
06
P06
Pump operation
0=Post-Circulation
1=Continuous
0=Post-Circulation
07
P07
Pump deactivation temperature dur-
ing Post-Circulation (P02=1)
0-100°C
35°C
Pump deactivation temperature dur-
ing Post-Circulation (P02=2)
0-100°C
35°C
Pump deactivation temperature dur-
ing Post-Circulation (P02=3)
0-100°C
35°C
Pump deactivation temperature dur-
ing Post-Circulation (P02=4)
0-100°C
35°C
Pump deactivation temperature dur-
ing Post-Circulation (P02=5)
0-100°C
35°C
Pump deactivation temperature dur-
ing Post-Circulation (P02=6)
0-100°C
35°C
08
P08
Heating user max. set point
31-90°C
80°C
09
P09
No function (P02=1)
--
--
DHW pump activation temperature
(P02=2)
0-80°C
40°C
DHW pump activation temperature
(P02=3)
0-80°C
40°C
DHW pump activation temperature
(P02=4)
0-80°C
40°C
No function (P02=5)
--
--
DHW pump activation temperature
(P02=6)
0-80°C
40°C
10
P10
DHW pump Post-Circulation
0-255 seconds
30 seconds
11
P11
DHW standby time
0-255 seconds
120 seconds
12
P12
DHW user max. set point (P02=1)
--
--
DHW user max. set point (P02=2)
55-65°C
65°C
DHW user max. set point (P02=3)
--
--
DHW user max. set point (P02=4)
--
--
DHW user max. set point (P02=5)
--
--
DHW user max. set point (P02=6)
55-65°C
65°C
13
P13
No function (P02=1)
--
--
Hot water tank activation hysteresis
temperature
(P02=2)
0-20°C
40°C
No function (P02=3)
--
--
No function (P02=4)
--
--
No function (P02=5)
--
--
Hot water tank activation hysteresis
temperature
(P02=6)
0-20°C
40°C
14
P14
No function (P02=1)
--
--
Hot water tank preparation delivery
temperature (P02=2)
70-85°C
80
Hot water tank preparation delivery
temperature (P02=3)
70-85°C
80
Delivery temperature adjustment in
DHW mode (P02=4)
50-65°C
55
Delivery temperature adjustment in
DHW mode (P02=5)
50-65°C
55
Hot water tank preparation delivery
temperature (P02=6)
70-85°C
80
15
P15
Boiler shell Warm-up activation tem-
perature (P02=1)
0-80°C
0°C
Boiler shell Warm-up activation tem-
perature (P02=2)
0-80°C
0°C
Boiler shell Warm-up activation tem-
perature (P02=3)
0-80°C
0°C
Comfort activation temperature
(P02=4)
0-80°C
55°C
Comfort activation temperature
(P02=5)
0-80°C
55°C
Boiler shell Warm-up activation tem-
perature (P02=6)
0-80°C
0°C
16
P16
Boiler shell Warm-up deactivation
hysteresis (P02=1)
0-20°C
5°C
Boiler shell Warm-up deactivation
hysteresis (P02=2)
0-20°C
5°C
Boiler shell Warm-up deactivation
hysteresis (P02=3)
0-20°C
5°C
Comfort deactivation hysteresis
(P02=4)
0-20°C
20°C
Comfort deactivation hysteresis
(P02=5)
0-20°C
20°C
Boiler shell Warm-up deactivation
hysteresis (P02=6)
0-20°C
5°C
17
P17
System min. pressure value
0-8 bar/10
2 bar/10
18
P18
System nominal pressure value
5-20 bar/10
6 bar/10
19
P19
No function (P02=1)
--
--
Legionella protection (P02=2)
0-7
0
No function (P02=3)
--
--
No function (P02=4)
--
--
No function (P02=5)
--
--
Legionella protection (P02=6)
0-7
0
20
P20
Mains Voltage Frequency
0=50Hz,1=60Hz
0=50Hz
t1
NTC Heating sensor (°C)
between 05 and 125°C
t2
NTC DHW sensor (°C)
(Only with Parameter P02=2, boiler with storage or with Parameter P02=6,
boiler with storage)
between 05 and 125°C
t3
NTC Safety sensor (°C)
between 05 and 125°C
t4
NTC External sensor (°C)
between -30 and 70°C
(Negative values flash)
P5 Actual system water pressure (bar/10)
00-99 bar/10
Remote
Control
Card
Description
Transparent Parameters
Range
Default