background image

20

(15190) PreLOG   

          Operating Instructions 

Operating Instructions
Data Logger PreLOG (15190)

9.2.2 

Setup – PreLOG Con

fi

 guration

The function “

PreLOG Con

fi

 guration

” is used to con

fi

 gure PreLOGs.

Tip: Please note that a PreLOG can only be con

fi

 gured if it is connected to the con

fi

 guring PC!

The window “

PreLOG Con

fi

 guration

” has 4 tabs: “

General

”, “

PreLOG Internal Communication

”, “

Alarm (Part 

1)

” and “

Alarm (Part 2)

.” In the tab “

General

” you can specify the “

Station Identi

fi

 cation

” and “

Operating Mode

” 

as well as the “

PC Settings

” for the communication. In the tab “

PreLOG Internal Communication

” you can 

specify the settings of the PreLOG for the communication via modem. For further information on the con

fi

 guration 

of the modem respectively the initialisation commands for the modem, please refer to chapter 9.2.4 (p. 22) and 
the documentation of the modem in use. In the tabs “

Alarm (Part 1)

” and “

Alarm (Part 2)

” you can de

fi

 ne certain 

events at which the PreLOG will transmit a standardised alarm message via GPRS modem.

General
Station Identi

fi

 cation

The “

Serial number

” and the date of the “

Last Con

fi

 guration

” will be obtained from the PreLOG which is selected 

under “

Setup – Select Current Station

.” They are used to identify the station. The standard station number is 

0001. This value should only be changed if, and only if, multiple PreLOG systems are in the same network or are 
used with GPRS communication. Numbers between 0001 and 9999 are allowed. 

Tip: The station number 

0

 ist reserved. Every PreLOG will react with it on requests, but no 

PreLOG can be con

fi

 gured to have the station number 

0

.”

If the station number of the PreLOG differs from the number saved in the PreLOG-Commander, please 

fi

 rst check 

if the correct station is selected (“

Setup – Select Current Station

”). If you know the station number, enter it in the 

fi

 eld and press the tabulator key. An “

Enter

” button will then appear, click on this to 

fi

 nish the process. Afterwards 

communication with the connected PreLOG should work again. If you do not know the station number, enter the 
station number “

0

” instead. “

Request CFG

” you receive the con

fi

 guration data of the connected station and thereby 

the current station number. Before closing the window save the data by pressing the “

Save

” button.

Operating Mode

Since the PreLOG is a pulse logger, it is mainly used to record amounts of precipitation over time. To use it this 
way one selects in the 

fi

 eld “

Time Base

” the duration in min over which the pulses are added up. If instead of a 

time “

Individual Pulses

” is selected, the PreLOG records each pulse with a corresponding timestamp. The pulses 

will be recorded with the speci

fi

 ed resolution factor or if necessary with the corresponding intensity-dependent 

corrected value and a timestamp. The sums are calculated respectively and recorded with timestamp, too.

In the 

fi

 eld “

Resolution Factor

” you can enter the amount of precipitation in mm/m² which corresponds to a 

tipping bucket pulse of the connected precipitation sensor. In case of precipitation sensors of the type 1518H3, 
15188 and 15189 this is 0.1 mm/pulse for the 2 cm³ tipping bucket and 0.2 mm/pulse for the 4 cm³ tipping bucket. 
If a rain[e] is connected, the resolution factor has to be selected in accordance to the rain[e] settings (smallest 
possible value: 0.01).

For LAMBRECHT precipitation sensors without an integrated precipitation correction or signal linearisation the 
PreLOG speci

fi

 c linearisation can be activated by checking the box for “

Signal Linearisation

.” It compensates 

the intensity-dependent measuring error due to the principle of tipping bucket precipitation sensors. It means that  
precipitation amounts (individual pulses as well as sums) will be recorded corrected depending on the intensity.

If needed the PreLOG can “

Calculate Sum Since Switch On

” (amount of precipitation since the PreLOG was 

switched on) and “

Calculate Sum Since Last Retrieval

.” These options can be activated with the corresponding 

check boxes. The recorded precipitation amount since the last retrieval will be reset to zero automatically after 
each retrieval. The values will be recorded and displayed in mm/m². Removing the battery and disconnection from 
any power supply will reset both values to zero, too.

 

Summary of Contents for 15190

Page 1: ...n intensity and without a modem Recharging of the battery via USB port Housing IP65 plugged in connector IP67 PreLOG Pulse output not corrected debounced Optional external power supply e g via solar s...

Page 2: ...ander p 19 9 1 Initial Configuration of a PreLOG Quickstart S 19 9 2 Setup p 19 9 2 1 Setup Select Current Station p 19 9 2 2 Setup PreLOG Configuration p 20 9 2 3 Setup Set PreLOG Clock p 24 9 2 4 Se...

Page 3: ...ines and or rules for the prevention of accidents e g 2 the professional association If necessary ask your responsible safety representative Use the system according to the manual s regulations only 3...

Page 4: ...OG ECO PreLOG 5 Mounting You can mount the PreLOG directly to the LAMBRECHT precipitation sensor 15189 Therefore the precipitation sensor is already delivered with the necessary bore or an appropriate...

Page 5: ...OG Operating Instructions Operating Instructions Data Logger PreLOG 15190 Another option is to mount the data logger to a mast with our special mast fixation from our traverse system Id No 32 14627 00...

Page 6: ...tor see Fig 04 1 Trim the supplied cable to the desired length and remove the sheath on 2 cm 2 Use a straight cut to remove the shielding braid up to the edge of the sheath 3 Cut the not used strands...

Page 7: ...t M12 Connector 8 Pin only PreLOG If the PreLOG should be read out via the RS232 interface externally powered or connected to the GPRS solar set the following pin assignment of the 8 pin M12 connector...

Page 8: ...Modem via RS232 GSM If the PreLOG should always be accessible the control pin RS232 Communication ON 4 has to be connected to the Masse GND pin This operating mode needs the most energy since both th...

Page 9: ...t retrieval or message Event message at exceeding of a max precipitation amount as moving sum of a specified period with hysteresis Event message at exceeding of a max precipitation intensity with hys...

Page 10: ...ers may result in incor rect measured values Therefore the intensity correction should be deactivated in such cases Since some LAMBRECHT precipitation sensors already have integrated intensity correct...

Page 11: ...me clock of the PreLOG is set by the function Setup Set PreLOG Clock of the PreLOG Commander By default the function suggests the date and time of the PC clock The circular buffer of the PreLOG can st...

Page 12: ...eLOG Commander function Retrieval PreLOG Status After this retrieval the value will be reset to zero too Example Precipitation in mm m 21 318 Configuration The recording of the precipitation amount be...

Page 13: ...e alarm Start of Precipitation can be activated in the PreLOG Commander in the tab Setup PreLOG Configuration Alarm Part 1 Furthermore the Amount Threshold in mm m as well as the Trigger Period period...

Page 14: ...will be released if the intensity falls below a specified release intensity Configuration The alarm Exceeding of a Max Precipitation Intensity can be activated in the PreLOG Commander in the tab Setu...

Page 15: ...ervice A well known example among others is DynDNS Such a dynamic DNS service automatically maps between the volatile IP address of the router that will change on every dial up but at the latest once...

Page 16: ...1 RS232 for GSM communication see pp 20 ff Connect the PreLOG to a PC or notebook via USB or serial connection RS232 Select the PreLOG and the modem option Standard PC under Setup Select Current Stat...

Page 17: ...Communication For the appropriate values see the corresponding sections in ch 9 2 2 on pp 20 ff and the documen tation of the modem in use if necessary Save and transmit the new configuration to the s...

Page 18: ...nto the MeteoWare data base With the function 4 Utilities export the data can be exported in the formats MW MeteoWare Rain specific ASCII dBASE and Excel To receive data from a station the PC has to b...

Page 19: ...of the ISO 8850 15 standard are allowed a Specify the COM port the PreLOG is connected to b Save the configuration by pressing the c Save button Retrieve the configuration of the connected PreLOG wit...

Page 20: ...n number enter the station number 0 instead Request CFG you receive the configuration data of the connected station and thereby the current station number Before closing the window save the data by pr...

Page 21: ...the connection if the communication starts right after the connection has been established The maximum number of dialing attempts can be specified in the field Max Redials If this limit is exceeded t...

Page 22: ...e some modem types will cancel the connection if the communication starts right after connection has been established The following access data are necessary for a GPRS connection APN Accesspoint addr...

Page 23: ...GPRS Test you can test if a GPRS connection can be established to the selected PreLOG In the process the command sequence to establish a connection via the selected GPRS modem will be executed by the...

Page 24: ...control sequence which suits the telephone system the modem is connected to It has to be distinguished between tone and pulse dial as well as between main station or telephone exten sion for further...

Page 25: ...ieval reset to zero afterwards Amount of Precipitation Since Switch On of the PreLOG Battery Status Percentage of Free Memory Most Recent GPRS Error Position of the Error in the Command Sequence The G...

Page 26: ...cription of these critical errors can be displayed with the function PreLOG Critical Error If a critical error occurs please check the PreLOG immediately and contact the LAMBRECHT service department 4...

Page 27: ...e LAMBRECHT service department and keep the entry from the GPRS LOG file within reach 10 3 Retrieval of PreLOG Configuration Failed Check in the tab Setup PreLOG Configuration General if the correct s...

Page 28: ...l 49 0 551 4958 0 or 49 0 551 4958 390 E mail support lambrecht net 12 Equipment and Spare Parts General Accessories 00 90519 000 000 GPRS solar set 36 09338 010 000 Software MeteoWare Rain basic 36 0...

Page 29: ...29 15190 PreLOG Operating Instructions Operating Instructions Data Logger PreLOG 15190 13 Space for Notes...

Page 30: ...on via USB with PreLOG Commander Real time Clock typ 3 ppm at 15 C 60 C max 5 ppm at 25 C 65 C max 10ppm Rechargeable Battery 3 6 Li Ion exchangeable Ext Power Supply 12 V DC 9 26 V DC Caution Power s...

Reviews: