background image

 

25 

 

 

During normal working mode, the following operations can be performed: 

  Stove power setting, choosing from one of the five available levels. Power setting is carried out via 

BUTTONS "6" to increase and "5" to decrease.  

  Programmable thermostat parameter setting (see later section). 

  Desired room temperature setting, choosing an interval from 7°C to 40°C. Press "2" once and then set the 

temperature with button "1" to increase and "2" to decrease. 

  Desired boiler temperature setting, choosing an interval from 30°C to 80°C. Press "1" once and then set 

the temperature with button "1" to increase and "2" to decrease. 

  View water circuit pressure. Press and hold button 5. 

 

Periodic brazier cleaning is also active during working mode. Brazier cleaning mode is activated at regular 

intervals of about one hour. In this way, the smoke extractor works at maximum power while pellet feeding is 

reduced to minimum. This operation is necessary for eliminating ash deposits inside the brazier and for 

ensuring proper aeration and combustion. During brazier cleaning, the display will show the message 

"BRAZIER CLEANING". 

If you notice excessive accumulation of pellets in the brazier during normal 

operation, turn off the stove immediately and contact a service centre. Forcing could make your stove 

a hazard.

 

6.3.4  Modulation based on room temperature 

The stove is equipped with an internal temperature sensor that allows it to modulate its power according to 

the desired room temperature. 

For correct environment sensor operation, verify that the thermostat sensor positioned in the rear of the stove 

under the outlet (see Figure 14) is away from the fume exhaust pipe and is not in contact with objects or walls. 

Press button "2" to set room temperature. The message " SET ROOM TEMP" will appear on the bottom of 

the display, while the upper part will show the set temperature.  

To modify this value, use buttons "1" and "2" until you reach desired temperature (7°C to 40°C). 

If the room temperature reaches the set temperature, the stove goes into minimum power and the last line of 

the display shows "MODULATE." This modulation has been completed only if the room temperature returns 

to being lower than the set temperature. In this case, the stove will return to the power set by the user and 

the display will show the message "MODULATE" and standard working indications will return. 

6.3.5  Modulation based on boiler water temperature 

The stove is equipped with boiler water temperature sensor that allows it to modulate its power according to 

the desired temperature. 

To set water temperature, press button "1". Press button "1" once and the bottom of the display will show the 

message " SET WATER TEMP", while the upper part of the display will show the set water temperature. To 

modify this value, use buttons "1" and "2" until you reach desired temperature (30°C to 80°C). 

We 

recommend setting water temperature in the boiler between 60° C and 70° C. 

Briefly press button "4" to exit from programming or wait a few seconds to automatically return to the work or 

stand-by position. 

During the working phase, if the water temperature in the boiler is much lower than the set value, the stove 

operates at the maximum power level set.  

However, when the boiler water temperature approaches the set value (difference of less than 3° C), the 

stove heater gradually decrements the power level. The last line of the display shows a flashing number that 

indicates the power level at which the stove is working at that moment. A decrease in water temperature will 

correspond to an increase of the power level until it returns to the maximum power value set initially. 

We 

recommend always setting Hydro stove power to its maximum value "5".  

If, despite reducing power, boiler water temperature continues to rise and reaches the set temperature, the 

bottom line of the display will show "MODULATE." If, despite modulation, the water temperature tends to rise 

Summary of Contents for IDRO HYDRO

Page 1: ...nance The instruction manual is an integral part of the product Laminox S r l reserves the right to change the characteristics and data reported in the following document at any time and without warni...

Page 2: ...le Connect the stove to the mains only after proper professional connection to the chimney flue The power cable plug must remain accessible after installation of the stove Only operate the stove with...

Page 3: ...4 5 2 Tubes and maximum usable lengths 14 4 5 3 Holes for exhaust tube passage on walls or roof recommended insulation and diameter 15 4 5 4 Using a traditional type chimney flue 15 4 6 Using an exter...

Page 4: ...haust pressure sensor 33 8 1 2 Boiler Structure temperature sensor 33 8 1 3 Smoke temperature sensor 33 8 1 4 Water temperature sensor 34 8 1 5 Water pressure switch 34 8 2 Alarms 34 9 WARNINGS AND MA...

Page 5: ...reater than 45 Fig 2 Each device must have its own chimney flue with a section equal to or greater than the diameter of the fume exhaust pipe of the stove and a height no less than the one stated Neve...

Page 6: ...tructed so as to prevent penetration into the flue of rain snow or foreign bodies and so that in the event of winds in any direction and at any angle it assures the discharge of combustion products wi...

Page 7: ...tion device The room adjacent to the permanent openings must meet the requirements set out in the paragraphs above The adjacent room cannot be used as a garage for storage of combustible material or f...

Page 8: ...see attached sheet 2 4 Product identification data see attached sheet The technical label shows device data and performance Tampering with removing or lack of a technical label makes installation and...

Page 9: ...rizontal splits Since pellet characteristics and quality greatly influence the autonomy efficiency and proper operation of the stove we recommend AVOID using pellets with dimensions different from tha...

Page 10: ...e installed in a technical room It is forbidden to install them in open verandas or outdoors Installation in rooms containing other generators that collect air from the environment is prohibited par 6...

Page 11: ...ch must always be guaranteed 4 2 1 Corner installation mm 4 2 2 Wall installation mm Safety distances from flammable material Minimum distance in air from the flammable rear wall P 200 Minimum distanc...

Page 12: ...12 4 2 3 Distance from flammable ceilings and false ceilings mm 4 2 4 Distance of fume exhaust system from flammable walls mm...

Page 13: ...for positioning air intake vents Pellet stove combustion air intake vents cannot be connected to an air distribution system or directly to a wall mounted air intake vent Correct and safe positioning o...

Page 14: ...equipment boilers hoods etc is prohibited 4 5 2 Tubes and maximum usable lengths Painted aluminised steel tubes minimum thickness 1 5 mm stainless steel tubes Aisi 316 or porcelain tubes minimum thic...

Page 15: ...is flammable or has flammable parts 100 280 300 Concrete wall or roof 50 180 200 Brick wall or roof 30 140 160 4 5 4 Using a traditional type chimney flue If you wish to use an already existing chimne...

Page 16: ...secured to the building Fig 13 should be used An inspection area should be created at the base of the duct for performing periodic checks and maintenance It should be equipped with a windproof chimney...

Page 17: ...orklifts cranes etc 5 2 Unpacking Unpack the product being careful not to damage or scratch it Remove the accessory package and any pieces of polystyrene or cardboard used to block removable parts etc...

Page 18: ...d with an additional and adequate closed appropriately dimensioned expansion vessel For the installation of an additional expansion vessel take into account that usually 1 litre of vase compensated 10...

Page 19: ...3 Pressure switch 4 Vent safety 5 System delivery 6 Flue gas motor 7 Primary air inlet 8 Expansion vessel 9 System return 10 Circulation pump 11 Power supply outlet 12 Main switch 13 Serial port 14 E...

Page 20: ...thermostat connected to the circuit board see electrical diagram The thermostat connection is made using a 2x0 5 mm2 cable This operation should be performed by qualified personnel If you choose to us...

Page 21: ...and the fame is always present in the brazier If the flame is extinguished a dense white smoke may form able to cause an explosion in the combustion chamber The explosion can be of such intensity as t...

Page 22: ...unctions increase in set power value passage from a sub menu to the next one BUTTON 3 MENU SELECTION Functions Passage to sub menus passage from programmable thermostat and clock programming passage t...

Page 23: ...r Fill up the system through a refill valve to be provided externally to the stove During recovery it is advisable not to exceed a maximum pressure of 1 bar Pressure can be read directly on the pressu...

Page 24: ...sage Third phase Stabilisation Once combustion triggering has been detected the third phase will start and the display will show the message FIRE PRESENT Pellet feeding is reduced and ventilation incr...

Page 25: ...ure To modify this value use buttons 1 and 2 until you reach desired temperature 7 C to 40 C If the room temperature reaches the set temperature the stove goes into minimum power and the last line of...

Page 26: ...The hot air fan will also continue to run until the stove cools down CAUTION Never disconnect the power supply at this stage as this may create problems for the stove and compromise the subsequent pha...

Page 27: ...Menu 01 WATER PRESSURE This item is only available on hydro and boiler models firmware update Dec 2010 and allows you to bypass pressure control when the heating stove or boiler is connected to an ope...

Page 28: ...After having set the first parameter M 3 2 01 DAILY CHRONO to on you can set two start ups and two shutdowns For each parameter you can either set the value off if you do not wish to activate or the t...

Page 29: ...on or off based on which programming you wish to activate corresponding to that day of the week See following tables PROGRAMME 1 menu level selection meaning possible values 03 03 02 START PROG 1 on...

Page 30: ...weekend programme only after having disabled weekly programming PROGRAMME 3 menu level selection meaning possible values 03 03 20 START PROG 1 on time 00 00 23 50 OFF 03 03 21 STOP PROG 1 off time 00...

Page 31: ...do not return under the set values the stove shuts off and goes into stand by mode During shutdown the display shows the message WAIT COOLING This display message remains until re lighting conditions...

Page 32: ...h unit pellet load times are increased or decreased by 2 5 7 11 Menu 11 FIREPLACE TYPE This menu allows users to simultaneously increase or decrease all smoke fan parameters draft The set default valu...

Page 33: ...as combustion parameters not adjusted correctly in particular the low power combustion parameters If the combustion chamber door is left open If pellet accumulates inside the brazier supply duct resul...

Page 34: ...8 1 5 Water pressure switch The water pressure switch is directly connected to the electronic board and keeps operating water temperature in the boiler under constant control allowing safe use of the...

Page 35: ...p phase a maximum waiting time about 20 minutes is exceeded without the machine switching on successfully see ignition AL 6 No pellet This alarm indicates a flame failure in the brazier during normal...

Page 36: ...ait and make sure that the combustion of pellets left in the brazier has been completed If necessary call a support centre to replace the sensor AL A Water temp This alarm is activated by the over tem...

Page 37: ...not allowing correct boiler operation and which must be removed Every two days remove the brazier by simply lifting it from its housing then clean it from ash and any incrustations which may have for...

Page 38: ...t a Technical Support Centre to replace 9 10 Replacing the remote control battery Replace the old battery with a type CR2025 3V new one paying attention not to invert the polarity polarity is shown on...

Page 39: ...smoke exhaust duct new silicone where required Inspection and checking the gasket seals replacement and silicone application where required Tank emptying and cleaning Checking the electrical part and...

Page 40: ...Laminox S r l Hydro Division Zona Industriale Callarella 261 263 62028 SARNANO MC Italy Tel 39 0733 657 622 Fax 39 0733 657 494 www laminox com e mail idro laminox com rev 1 2021 EN...

Reviews: