H2
Automatic
The basis for an even room temperature is a characteristic heating
curve of just the right shape. The right shape for a characteristic
heating curve depends on many factors.
In 203GT the characteristic heating curve can be
adapted to exactly meet the needs of the facility from three points;
203GT prevents the setting of an incorrectly shaped charac-
teristic heating curve. It automatically suggests an adjustment.
1. outdoor temperature of -20 C
2. outdoor temperature of
0 C
3. outdoor temperature of +20 C
o
o
o
Press
Press the
or
button to set the supply water temperature at an outdoor
temperature of -20 C.
o
Press
OK.
OK.
-
+
Press
ESC
until the display no longer changes.
You are then in the "Selection" display shown in the adjoining picture.
Use the
button to move from one regulating circuit to the next
(H1, H2).
Press the
button to move cursor to "Heating curve"
Press
OK.
SETTINGS FOR HEATING CURVE
OPERATING INSTRUCTION:
80
65
50
35
20
20 0 -20 °C
80
65
50
35
20
20 0 -20 °C
80
65
50
35
20
20 0 -20 °C
Press
OK.
H1
Outdoor
°C
SupplyTemp
°C
Selection
Automatic
-15
52
H1 Curve:
-20 =
°C
20 = 21°C
0 = 27°C
+
32
H1 Curve:
-20 = 32°C
20 = 21°C
0 =
°C
+
27
H1 Curve:
-20 = 32°C
0 = 27°C
+20 =
°C
21
CURVE INTERPRETATION:
When the outdoor temp. is:
-20 C, the supply water is +32 C
0 C, the supply water is +27 C
+20 C, the supply water is +21 C
The temperature of the supply water may vary from the curve
if a reduced operation mode, room, wind or sun compensation
has been connected to the regulator or if one of the limiting functions
limits the temperature (see p. 11).
If the outdoor sensor is disconnected or if the sensor is broken,
the regulator assumes that the outdoor temperature is 0 C (use during
construction without the outdoor sensor).
o
o
o
o
o
o
o
Attention!
80
65
50
35
20
20 0 -20 °C
H1 Curve:
-20 = 32°C
0 = 27°C
+20 = 21°C
Supply
water
temperature
Outdoor temperature
4
1
2
3
H1 Select
Heating curve
Settings
Measurements
Info water temp
Operat. modes
Clock functions
Language/Keel
Type info
Start function
Mainten. mode
Press
Press the
or
button to set the supply water temperature at an outdoor
temperature of 0 C.
o
Press
OK.
OK.
-
+
Press
Press the
or
button to set the supply water temperature at an outdoor
temperature of -20 C.
Exit with
o
Press
OK.
OK.
-
+
ESC.