Ajan asetus
Explanation:
Range:
Factory
Settings
Settings:
Attention!
Additional information about settings
The automatic pre-increase in degrees which
occurs after a reduced operation (nighttime drop)
The pre-increase makes it possible to raise the
room temperature faster to a nominal room
temperature (day temp.) after a reduced
operation. A maintenance person must set the
length of the pre-increase time (see maintenance
mode p 21).
In autumn, the temperature of the supply water is
automatically raised for 20 days through autumn
drying. Autumn drying is activated when the
average temperature in a 24-hour period has
continually been above 7 °C for a period of at
least 20 days and after this drops below 7 °C.
Autumn drying is activated during the next 20
days whenever the average temperature in a 24-
hour period is under 7 °C.
The autumn drying
setting indicates how much autumn drying raises
the supply water temperature. The original factory
setting is 1 °C.
Pre-increase
Autumn dry
Valve close
Pre-increase time
(A mainten. person set)
Nominal
temperature
Reduced temp.
= night drop
Menovesi
°C
Room temp.
Spared energy
Average temp.
In a 24-hour
(Outdoor temp.)
A time period
of at least
20 days
7 °C
7 °C
Autumn drying - function on
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Time/day
Average 24-hours
temp. curve
c
1.5 °C
The setting appears if
pre-increase time has
been set in
maintenance level
settings. (see p. 21)
7
0.0...7.0°C
Valve closed during the summer:
The
outdoor
temperature limit at which the regulator closes the
valve in H1 circuit. Circuit 2 is often used to warm
up the wet places (sauna stove, lavatory and so on)
Because it is important to warm up the wet places
also summer time, the valve in circuit 2 is not closed.
Room compens.
Room compensation ratio: If the room
temperature is different than what it is set at,
the room compensation corrects the supply
water temperature. (Eg.) If the room
compensation is 4 and the room temperature
has risen 1,5
above the setting, the regulator
drops the supply water temperature 6
(4x1,5
=6
).
°C
°C
°C
°C
An appropriate room
compensation ratio for floor heating is usually
between 1.5 - 2.0°C.
Room sensor
(TMR)
must be connected
(H1:meas.3,
H2:meas. 6, or net).
A house cools down in windy weather. In that
case the wind compensation raises the supply
water temperature. The reading indicates the
maximum amount that the wind compensation
can raise the supply water temperature.
The room temperature of a house having large
windows with a south exposure rises on a sunny
day even in subzero weather. The reading
indicates the maximum amount that the sun
compensation can drop the supply water temp.
0 °C
0 °C
must
be connected, the
same sensor for
regul. circuits H1 and
H2 (meas. 6 or net).
Sun sensor
0... 7 °C
0...-7 °C
Sun compens.
Wind.compens.
Wind sensor
must
be connected, the
same sensor for
regul. circuits H1 and
H2 (meas. 6 or net).
0°C
2 °C
20°C
0...25 °C
0...15 °C
5...50 °C