background image

20

100% GEOTHERMAL HEAT

20

INSTALLER MANUAL

• 

External supply is connected to terminals A1 and A2.

• 

Terminals 15 and 16 are connected to geothermal heat pump and 
interrupt the heating element’s supply with respect to the phase the 
current value of which is exceeded.

• 

Each phase must be lead through the relay using the dedicated hole 
inside it: L1 for relay 1, L2 for relay 2, L3 for relay 3

No other connections with relay are necessary.

4.3.4. Electrician’s checklist

Check that

• 

all phases going to the switchboard are in the correct phase 

sequence

• 

the master fuse is of sufficient size

• 

the ground source heat pump’s fuse size is correct, type: slow (C 

curve)

• 

if necessary, current monitor has been installed to the building’s 
master electrical switchboard (part-power models)

If  the  ground  source  heat  pump  is  started  for  the  first  time  without 
pre-heating,  compressor  will  be  damaged.  Fill  the  storage  tank  with 
water and prevent the compressor from starting by pressing down the 
red compressor motor circuit breaker. Switch on the ground source heat 
pump’s power supply, the electric heating element begins to heat the 
water contained in storage tank. A regulator alarm goes on and the text 
“Compressor 1 circuit 1 some motor protection gone off. Check motor 
protection F1, F2 or F3” appears on the display. Later another regulator 
alarm goes on and the text “Resistor functioned in full power system” 
appears. These alarms do not require taking any measures. Starting of 
the compressor is allowed after six hours of pre-heating.

NOTE! A COMPRESSOR STARTED WITHOUT PRE-

HEATING IS NOT COVERED BY WARRANTY! 

4.4. Commissioning 

Before commissioning, check that: 

• 

the heating system has been connected, filled and de-aerated 

appropriately 

• 

the ground circuit has been installed, filled and de-aerated 

appropriately 

• 

electrical connections have been made appropriately and the 

outdoor sensor (and optional room sensor) has been installed 

• 

after preventing the compressor from starting, water in the 

storage tank has been heated by the electric heating element for 
at least 6 hours 

Possible problems during startup

Problem 

Cause 

Solution 

Fuses always blow 
when the compressor is 
started.

You are using the wrong 
type of fuse.

Check that the fuse 
is automatic: C or D / 
ceramic fuse: SLOW or 
with a snail icon. 

Temporary connections 
at the site are causing an 
overload of the fuses

Reduce load. 

The heat collection 
circuit pump does not 
start.

The regulator may not be 
getting any power.

Check the regulator fuse.

The regulator is not au

-

thorised to start the pump.

Check the measured/set 
values.

The shut-off valves are in 
the fill position.

Check that the de-
aeration and fill valves 
are in the closed position 
and that the intermedi

-

ate valve is open. 

The heat collection 
circuit’s water circulation 
pump motor protection 
switch has gone off.

Reset the motor protec

-

tion switch and check 
the set values from 
electrical diagram.

The compressor runs 
for a little while and 
the evaporator pressure 
switch goes off.

There may still be air in 
the heat collection circuit.

De-aerate the heat col

-

lection circuit.

There may be a leak in the 
refrigerant circuit. 

Contact the equipment 
installer or dealer. 

The fluid level in the 
heat collection circuit fill 
container drops suddenly 
after startup. 

There is a leak in the 
system (the smell of ethyl 
alcohol or glycol is strong), 
there is a leak in the heat 
collection circuit or there 
is still air in the circuit. 

Check the condition of 
valves in the de-aeration 
group, air valve and the 
shaft seal on the ground 
circuit pump, check the 
condition of heat col

-

lection circuit extension 
joints, or de-aerate.

Motor protection 
switches go off when 
starting. 

The compressor or the 
ground circuit pump is 
short-circuited or one 
of the phases is not 
activated.

Check electrical connec

-

tions. 

The fuses in the master 
switchboard of the build

-

ing have blown or are 
faulty.

Check and replace fuses 
as required. 

The maintenance menu section Manual control allows manual control of 
compressors, pumps and valves. This facilitates troubleshooting process 
and may be of help in case of starting problems.

Summary of Contents for VMI 6-17

Page 1: ...L MP SS Vmi 6 17 L MP SS 3 2016 INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE...

Page 2: ...L mp ss for many decades to come Please familiar ize yourself with these instructions for use and maintenance Keep the instructions for future use and reference should problems occur These instructio...

Page 3: ...rt 15 4 1 2 Ground source heat pump installation area 15 4 1 3 Removing the packaging 15 4 1 4 Space requirements 16 4 2 HVAC installation 16 4 2 1 Heat collection circuit and fill group installation...

Page 4: ...storage tank Heat collection circuit Heating water Domestic water Compressor Evaporator Superheater Condenser Press this button for additional information on the touch screen data The type plate of th...

Page 5: ...5 Expansion valve 6a Upper storage tank 6b Lower storage tank 7a Upper storage tank domestic water coil 7b Lower storage tank domestic water coil 2 1 2 Compressor unit From the evaporator refrigerant...

Page 6: ...oil into two parts allows heating of the domestic water circulation only using the upper storage tank coil so that blending of the storage tank temperature stratifications is avoided 2 2 ss Cooling co...

Page 7: ...the bottom left corner to return to the home screen Use the arrow button in the bottom right corner to return to previous screen For instructions screen press the i button in the top right corner In...

Page 8: ...s which can be accessed by pressing the button at the bottom centre of the screen In case of compen sation value 7 the adjustment is seven times faster than in case of value 1 Large compensation value...

Page 9: ...nd date or time is in the future If the end date is set into the past the mode Home is activated and the mode Away cannot be activated 3 4 5 Measurements This shortcut allows accessing the Measurement...

Page 10: ...ustment curves are set higher than the storage tank temperature Factory settings for the storage tank bottom section are 40 C min and 45 C max Factory settings for the storage tank top section are 50...

Page 11: ...ther modifications in adjustment curve set values When using radiator heating temperature change is quicker Conditions in Finland pumps and 60 C bottom section 85 C top section in case of part power g...

Page 12: ...it value between 0 90 C factory set ting 55 C 3 5 3 Other set values The menu Other set values allows circuit specific programming of maxi mum and minimum heat distribution circuit supply water values...

Page 13: ...erature is not achieved by the com pressor during the dedicated period from 0 to 24 hours factory setting 12 hours The setting is applicable in full power systems only 3 5 3 5 Bivalent settings in biv...

Page 14: ...a Use the screen numbering in the bottom bar for navigating between the Measurements screens Measurements screen values describe heat pump operation under various conditions and the values shown canno...

Page 15: ...ource heat pump s accessory package includes adjustable feet to be screwed into the unit bottom see picture After that remove the wooden platform elements and their fixation screws 4 pc To remove the...

Page 16: ...1 with a frost resistance of 16 C reinforced hose 1 2 pc length approx 3 m connector 3 4 female thread for reinforced hose connector 1 female thread for reinforced hose WORK STAGES Please check that...

Page 17: ...11 J hdytys paluu Cooling return 1 12 Aurinkoyhde meno Solar connection flow 13 Aurinkoyhde paluu Solar connection return 14 Kv kierto Hot water circulation Varaajan t yt n yhteydess varaajassa oleva...

Page 18: ...unit The mixing valve is fitted to the hot water pipe in order to prevent burns The overflow pipe is joined to the floor drain as instructed or to an overflow funnel if the distance to the floor drai...

Page 19: ...ormal outdoor temperature Device Terminal block No Conductor type Outdoor sensor NTC X1 10 ja X1 2 2 X 0 7 mm2 4 3 2 Room sensor optional In order for the room sensor to detect average indoor temperat...

Page 20: ...from starting water in the storage tank has been heated by the electric heating element for at least 6 hours Possible problems during startup Problem Cause Solution Fuses always blow when the compres...

Page 21: ...condition of the fuses in the master switchboard Incorrect power supply phase sequence Contact an electrician The compressor does not start and the display reads Incor rect phase sequence or Motor pro...

Page 22: ...t of heat is needed for example the outdoor tem perature is very low or the structure is drying during the first year s use of the building No action required Lack of refrigerant Can be detected from...

Page 23: ...e alarm circuit 1 3 Brine pump 1 Run indicator 12 Compressor 1 Run indicator 4 13 5 14 Soft Starter 6 15 External Alarm 7 Compressor 1 internal alarm 16 8 17 Flow Sensor 9 Phase failure detector 18 Di...

Page 24: ...t water sensor 4 Boiler foot part temperature sensor 9 Inside temperature sensor 5 Outside temperatur sensor 10 Brine temperature sensor Analog outputs This screen allows checking analog output status...

Page 25: ...ivative time the more the regulator position changes upon each adjust ment Consider that increase in derivative time may result in increased regulator fluctuation Voltage 0 10 V Position valve control...

Page 26: ...method to use 5 4 9 Temperature gauges This screen allows choosing the temperature gauges used By default the outdoor temperature gauge is present Indoor temperature gauge is optional 5 4 10 External...

Page 27: ...percentage indicated in the valve setting point L mp ss unit Factroy setting Vmi 6 11 30 Vmi 14 17 40 5 4 13 Boiler maximum limits Maximum boiler limits are set on this page 5 4 14 Cooling Selectable...

Page 28: ...ions over 10 of the nominal voltage lightning fire or other respective event Transport damages are not covered by the warranty Also the warranty does not cover situations WARRANTY CONDITIONS caused by...

Page 29: ...rve 3 Constant curve 3 Constant curve 3 Factory setting of superheat circuit 30 35 35 35 40 40 40 Sound power level 1 dB 38 41 36 41 38 43 42 OPERATION LIMITS Temperature limits brine water C 10 60 15...

Page 30: ...48 0 59 0 70 0 68 0 89 0 83 1 00 Maximum external pressuredrop kPa 66 65 96 100 84 91 77 HEAT DISTRIBUTION CIRCUIT Energy class of HC pump A inverter A inverter A inverter A inverter A inverter A inv...

Page 31: ...XL 2015 811 2013 A A A B C D E F G A A A B C D E F G Vmi 6 38 dB 00 dB 8 kW 8 kW 8 kW...

Page 32: ...A A A A A A A A B C D E F G A A A A B C D E F G XL 2015 811 2013 XL X Vmi 6...

Page 33: ...Colder 4786 kWh a Warmer 2695 kWh a Annual electricity consumption for water heating under colder and warmer climate conditions Colder 1251 kWh a Warmer 1251 kWh a Energy efficiency for space heating...

Page 34: ...2 C Operation limit temperatures Heating Average TOL 10 C Warmer TOL 22 C Colder TOL 2 C Seasonal electricity consumption Heating Average QHE A 4116 kWh a Warmer QHE W 4786 kWh a Colder QHE C 2695 kW...

Page 35: ...XL 2015 811 2013 A A A B C D E F G A A A B C D E F G Vmi 9 41 dB 00 dB 10 kW 10 kW 10 kW...

Page 36: ...A A A A A A A A B C D E F G A A A A B C D E F G XL 2015 811 2013 XL X Vmi 9...

Page 37: ...s Colder 6181 kWh a Warmer 3418 kWh a Annual electricity consumption for water heating under colder and warmer climate conditions Colder 1308 kWh a Warmer 1308 kWh a Energy efficiency for space heatin...

Page 38: ...alent 2 C Operation limit temperatures Heating Average TOL 10 C Warmer TOL 22 C Colder TOL 2 C Seasonal electricity consumption Heating Average QHE A 5296 kWh a Warmer QHE W 6181 kWh a Colder QHE C 34...

Page 39: ...XL 2015 811 2013 A A A B C D E F G A A A B C D E F G Vmi 11 36 dB 00 dB 11 kW 11 kW 11 kW...

Page 40: ...A A A A A A A A B C D E F G A A A A B C D E F G XL 2015 811 2013 XL X Vmi 11...

Page 41: ...ns Colder 6899 kWh a Warmer 3837 kWh a Annual electricity consumption for water heating under colder and warmer climate conditions Colder 1214 kWh a Warmer 1214 kWh a Energy efficiency for space heati...

Page 42: ...Tbivalent 2 C Operation limit temperatures Heating Average TOL 10 C Warmer TOL 22 C Colder TOL 2 C Seasonal electricity consumption Heating Average QHE A 5296 kWh a Warmer QHE W 6899 kWh a Colder QHE...

Page 43: ...XL 2015 811 2013 A A A B C D E F G A A A B C D E F G Vmi 11 1x230V 41 dB 00 dB 11 kW 11 kW 11 kW...

Page 44: ...A A A A A A A A B C D E F G A A A A B C D E F G XL 2015 811 2013 XL X Vmi 11 1x230V...

Page 45: ...tions Colder 7106 kWh a Warmer 3908 kWh a Annual electricity consumption for water heating under colder and warmer climate conditions Colder 1267 kWh a Warmer 1267 kWh a Energy efficiency for space he...

Page 46: ...Tbivalent 2 C Operation limit temperatures Heating Average TOL 10 C Warmer TOL 22 C Colder TOL 2 C Seasonal electricity consumption Heating Average QHE A 6082 kWh a Warmer QHE W 7106 kWh a Colder QHE...

Page 47: ...XL 2015 811 2013 A A A B C D E F G A A A B C D E F G Vmi 14 38 dB 00 dB 14 kW 14 kW 14 kW...

Page 48: ...A A A A A A A A B C D E F G A A A A B C D E F G XL 2015 811 2013 XL X Vmi 14...

Page 49: ...ns Colder 8645 kWh a Warmer 4819 kWh a Annual electricity consumption for water heating under colder and warmer climate conditions Colder 1210 kWh a Warmer 1210 kWh a Energy efficiency for space heati...

Page 50: ...Tbivalent 2 C Operation limit temperatures Heating Average TOL 10 C Warmer TOL 22 C Colder TOL 2 C Seasonal electricity consumption Heating Average QHE A 7443 kWh a Warmer QHE W 8645 kWh a Colder QHE...

Page 51: ...XL 2015 811 2013 A A A B C D E F G A A A B C D E F G Vmi 14 1x230V 43 dB 00 dB 14 kW 14 kW 14 kW...

Page 52: ...A A A A A A A A B C D E F G A A A A B C D E F G XL 2015 811 2013 XL X Vmi 14 1x230V...

Page 53: ...tions Colder 9032 kWh a Warmer 5014 kWh a Annual electricity consumption for water heating under colder and warmer climate conditions Colder 1334 kWh a Warmer 1334 kWh a Energy efficiency for space he...

Page 54: ...Tbivalent 2 C Operation limit temperatures Heating Average TOL 10 C Warmer TOL 22 C Colder TOL 2 C Seasonal electricity consumption Heating Average QHE A 7627 kWh a Warmer QHE W 9032 kWh a Colder QHE...

Page 55: ...XL 2015 811 2013 A A A B C D E F G A A A B C D E F G Vmi 17 42 dB 00 dB 17 kW 17 kW 17 kW...

Page 56: ...A A A A A A A A B C D E F G A A A A B C D E F G XL 2015 811 2013 XL X Vmi 17...

Page 57: ...s Colder 10145 kWh a Warmer 5634 kWh a Annual electricity consumption for water heating under colder and warmer climate conditions Colder 1272 kWh a Warmer 1272 kWh a Energy efficiency for space heati...

Page 58: ...Tbivalent 2 C Operation limit temperatures Heating Average TOL 10 C Warmer TOL 22 C Colder TOL 2 C Seasonal electricity consumption Heating Average QHE A 8716 kWh a Warmer QHE W 10145 kWh a Colder QHE...

Page 59: ...e front part mas ter fuses 25 A Hysteresis 21 Current 25 28 Delay 1s The relay requires external voltage 24 240 V AC External supply is connected to terminals A1 and A2 Terminals 15 and 16 are connect...

Page 60: ......

Page 61: ......

Page 62: ......

Page 63: ......

Page 64: ......

Page 65: ......

Page 66: ......

Page 67: ......

Page 68: ......

Page 69: ......

Page 70: ......

Page 71: ......

Page 72: ......

Page 73: ......

Page 74: ......

Page 75: ......

Page 76: ......

Page 77: ......

Page 78: ......

Page 79: ......

Page 80: ......

Page 81: ......

Page 82: ......

Page 83: ......

Page 84: ......

Page 85: ......

Page 86: ......

Page 87: ......

Page 88: ......

Page 89: ......

Page 90: ......

Page 91: ......

Page 92: ......

Page 93: ...L mp ss is a trademark of Suomen L mp pumpputekniikka Oy We reserve the right to make changes Suomen L mp pumpputekniikka Oy Unikontie 2 62100 Lapua www lampoassa com R...

Reviews: