21
MAINTENANCE MANUAL
5. MAINTENANCE
5.1. Maintenance and care
The Lämpöässä ground source heat pump is an easy-care and reliable
heating system that does not require regular maintenance. If the installa
-
tion is carried out with care and in accordance with the instructions pro
-
vided, there is usually no need for maintenance. The fill container and
mixture circuit filter should be checked every couple of weeks during the
first few months and afterwards approximately once a month for the first
year of use thereafter.
Lämpöässä heat pumps which includes 3-6 kg refrigerant are hermatically
sealed and therefore annual inspection is not required. You are offered the
possibility of concluding an agreement on periodic inspections, in connec
-
tion with which the operation of the Lämpöässä heat pump is covered
stage by stage. The observations are registered in the inspection record
and necessary measures taken (such as adjustments, for example). For
additional information on the periodic inspection agreement, visit huolto@
lampoassa.fi.
5.2. Possible problems occurring during use
Problem
Possible cause
Solution
The compressor does
not start.
The water tank temperature
is adequate and in accor
-
dance with the regulator.
No action required.
The compressor has been
stopped for less than 1
minutes.
No action required.
Fuse problem.
Check the condition of
the fuses in the master
switchboard.
Incorrect power supply
phase sequence.
Contact an electrician.
The compressor does
not start and the
display reads Incor
-
rect phase sequence
or Motor protection
switch gone off.
Incorrect power supply
phase sequence.
Contact an electrician.
The motor protection switch
has gone off.
Check the motor protection
switch adjustment values,
set the motor protection
switch to Start position
and acknowledge the alarm
text displayed. If the fault
is not cleared, contact an
electrician.
The compressor does
not start and the
display reads Low
pressure switch gone
off or High pressure
switch gone off.
The low pressure switch has
gone off.
Check functionality of
the brine circuit pump
by running it through the
maintenance menu and
acknowledge the alarm text
displayed.
The high pressure switch
has gone off.
Check functionality of the
condenser pump by running
it through the maintenance
menu and acknowledge the
alarm text displayed.
The compressor
does not start and
the display reads
Divergence alarm
reading 4 compres
-
sor operation.
The motor protection switch
has gone off.
Press down the motor
protection switch.
The suction pressure switch
on the pressure switch has
gone off.
Set off the switch.
No text is visible on
the display.
The device is not getting
any power.
Check that that the control
current and master switches
are on.
A fuse has blown.
Check the building’s master
fuse and heat pump supply
fuse.
The display is damaged or
the display cable loose or
damaged.
Contact maintenance
Summary of Contents for VMI 6-17
Page 1: ...L MP SS Vmi 6 17 L MP SS 3 2016 INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE...
Page 31: ...XL 2015 811 2013 A A A B C D E F G A A A B C D E F G Vmi 6 38 dB 00 dB 8 kW 8 kW 8 kW...
Page 32: ...A A A A A A A A B C D E F G A A A A B C D E F G XL 2015 811 2013 XL X Vmi 6...
Page 35: ...XL 2015 811 2013 A A A B C D E F G A A A B C D E F G Vmi 9 41 dB 00 dB 10 kW 10 kW 10 kW...
Page 36: ...A A A A A A A A B C D E F G A A A A B C D E F G XL 2015 811 2013 XL X Vmi 9...
Page 39: ...XL 2015 811 2013 A A A B C D E F G A A A B C D E F G Vmi 11 36 dB 00 dB 11 kW 11 kW 11 kW...
Page 40: ...A A A A A A A A B C D E F G A A A A B C D E F G XL 2015 811 2013 XL X Vmi 11...
Page 44: ...A A A A A A A A B C D E F G A A A A B C D E F G XL 2015 811 2013 XL X Vmi 11 1x230V...
Page 47: ...XL 2015 811 2013 A A A B C D E F G A A A B C D E F G Vmi 14 38 dB 00 dB 14 kW 14 kW 14 kW...
Page 48: ...A A A A A A A A B C D E F G A A A A B C D E F G XL 2015 811 2013 XL X Vmi 14...
Page 52: ...A A A A A A A A B C D E F G A A A A B C D E F G XL 2015 811 2013 XL X Vmi 14 1x230V...
Page 55: ...XL 2015 811 2013 A A A B C D E F G A A A B C D E F G Vmi 17 42 dB 00 dB 17 kW 17 kW 17 kW...
Page 56: ...A A A A A A A A B C D E F G A A A A B C D E F G XL 2015 811 2013 XL X Vmi 17...
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 75: ......
Page 76: ......
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ......