167
8
Options
No.
Device Description
Attribute
0040
BT300
Operating mode of firing rate controller
Operating mode of firing rate controller
0 = OFF
1 = constant control
2 = controlled by atmospheric conditions/external setpoint shift
3 = external firing rate (software version BT300 v 3.3 and LCM100 v1.4 and higher)
Group: 20
Min.: 0
Max.: 3
Default: 0
Write: 1/UI
Version: 1.0.0.0
0048
BT300
Controller setpoint 1 (for constant control/minimum value for control by atmospheric
condition) [°C] [bar]
Controller setpoint 1 minimum
Setting the setpoint minimum for the controller controlled by atmospheric conditions in
°C or bar.
The setting is active if the input ’Setpoint changeover’ = 0.
If the firing rate controller is configured as a constant controller, setpoint 1 is set here.
Group: 20
Min.: 0
Max.: 999
Default: 75
Write: 0/UI
Version: 1.0.0.0
0049
BT300
Controller setpoint 1 maximum value (only for control by atmospheric conditions) [°C]
[bar]
Controller setpoint 1 maximum
Enter the setpoint maximum for the controller controlled by atmospheric conditions in
°C or bar.
The setting is active if the input ’Setpoint changeover’ = 0.
If the burner firing rate controller is set to constant control, this parameter is not active.
Group: 20
Min.: 0
Max.: 999
Default: 75
Write: 0/UI
Version: 1.0.0.0
0050
BT300
Controller setpoint 2 (constant control/minimum value for control by atmospheric con-
ditions) [°C] [bar]
Controller setpoint 2 minimum
Enter the setpoint minimum for the controller controlled by atmospheric conditions in
°C or bar.
The setting is active if the input ’Setpoint changeover’ = 1.
If the firing rate controller is configured as a constant controller, setpoint 2 is set here.
Group: 20
Min.: 0
Max.: 999
Default: 60
Write: 0/UI
Version: 1.0.0.0
0051
BT300
Controller setpoint 2 maximum value (only for control by atmospheric conditions) [°C]
[bar]
Controller setpoint 2 maximum value
Enter the setpoint minimum for the controller controlled by atmospheric conditions in
°C or bar.
The setting is active if the input ’Setpoint changeover’ = 1.
If the burner firing rate controller is set to constant control, this parameter is not active.
Group: 20
Min.: 0
Max.: 999
Default: 60
Write: 0/UI
Version: 1.0.0.0
0052
BT300
Firing rate controller: Lower limit [°C] [digit]
Summary of Contents for BT300 BurnerTronic
Page 2: ......
Page 25: ...24 3 Product Description Fig 3 9 Temperature derating BT300 for operation 2000 m NHN...
Page 49: ...48 4 Design and Functions Fig 4 20 Oil with pilot burner BT300...
Page 50: ...49 4 Design and Functions Fig 4 21 Oil without pilot burner BT300...
Page 51: ...50 4 Design and Functions Fig 4 22 Gas with pilot burner and leakage test BT300...
Page 52: ...51 4 Design and Functions Fig 4 23 Gas without pilot burner and leakage test BT300...
Page 53: ...52 4 Design and Functions Fig 4 24 Oil without pilot burner BT335...
Page 54: ...53 4 Design and Functions Fig 4 25 Gas without pilot burner and leakage test BT335...
Page 59: ...58 4 Design and Functions Fig 4 28 Leakage test process diagram...
Page 98: ...97 6 Operating Control and Displays...
Page 99: ...98 6 Operating Control and Displays...
Page 103: ...102 6 Operating Control and Displays...
Page 105: ...104 6 Operating Control and Displays...
Page 106: ...105 6 Operating Control and Displays...
Page 107: ...106 6 Operating Control and Displays...
Page 109: ...108 6 Operating Control and Displays...
Page 126: ...125 6 Operating Control and Displays 6 3 4 2 Curve Table Fig 6 37 Curve table window...
Page 246: ...242 10 EU Declaration of Conformity 10 EU Declaration of Conformity...
Page 247: ...243 10 EU Declaration of Conformity...