18
3
Product Description
Burner sequencer and fuel/air ratio control can be adjusted for a wide range of combustion
conditions by setting parameters. The BT300 for oil and gas can be set to start with and with-
out pilot burner. The integrated leakage test can be run before ignition or after shutting down
the burner.
Starting without pre-purge using gas is available in accordance with EN676.
The setting of fuel/air ratio curves can be optimised using optional CO/O
2
control during op-
eration. This helps to counteract conditions that interfere with combustion. This ensures a per-
manent burner operation at the greatest possible efficiency.
Operating and fault messages are displayed by symbols and numbers on UI300 User Inter-
face. Plant-specific configurations and settings of fuel/air ratio control curves are operated via
menu of UI300 User Interface.
An operating and start-up counter is integrated.
The optional LCM100 power control unit with two setpoints, external setpoint shift (control by
atmospheric condition) and start-up control is also available.
3.2
Life Cycle
The device has a designed lifetime
1
of 250,000 burner start-up cycles, which, under normal
operating conditions in heating mode, correspond to approx. 10 years of usage (starting from
the production date given on the type plate).
This lifetime is based on the endurance tests specified in standard EN230/EN298 and the ta-
ble containing the relevant test documentation as published by the European Association of
Component Manufacturers (Afecor) (www.afecor.org).
The designed lifetime is based on use of the device according to the manufacturer’s basic doc-
umentation. After reaching designed lifetime in terms of number of burner start-up cycles, or
the respective time of usage, the device must be replaced by authorized personnel.
3.3
Technical Data BurnerTronic BT300
Fig. 3-1 BurnerTronic BT300
•
BT341
Same range of functions as BT340 but also including following certificates:
DIN EN 61508:2002 parts 1-7 for SIL 3
Performance Level PLE according DIN EN ISO 13849-1
1
The designed lifetime is not the warranty time specified in the Terms of Delivery
Summary of Contents for BT300 BurnerTronic
Page 2: ......
Page 25: ...24 3 Product Description Fig 3 9 Temperature derating BT300 for operation 2000 m NHN...
Page 49: ...48 4 Design and Functions Fig 4 20 Oil with pilot burner BT300...
Page 50: ...49 4 Design and Functions Fig 4 21 Oil without pilot burner BT300...
Page 51: ...50 4 Design and Functions Fig 4 22 Gas with pilot burner and leakage test BT300...
Page 52: ...51 4 Design and Functions Fig 4 23 Gas without pilot burner and leakage test BT300...
Page 53: ...52 4 Design and Functions Fig 4 24 Oil without pilot burner BT335...
Page 54: ...53 4 Design and Functions Fig 4 25 Gas without pilot burner and leakage test BT335...
Page 59: ...58 4 Design and Functions Fig 4 28 Leakage test process diagram...
Page 98: ...97 6 Operating Control and Displays...
Page 99: ...98 6 Operating Control and Displays...
Page 103: ...102 6 Operating Control and Displays...
Page 105: ...104 6 Operating Control and Displays...
Page 106: ...105 6 Operating Control and Displays...
Page 107: ...106 6 Operating Control and Displays...
Page 109: ...108 6 Operating Control and Displays...
Page 126: ...125 6 Operating Control and Displays 6 3 4 2 Curve Table Fig 6 37 Curve table window...
Page 246: ...242 10 EU Declaration of Conformity 10 EU Declaration of Conformity...
Page 247: ...243 10 EU Declaration of Conformity...