29
3
Product Description
NOTICE
Damage of the actuator with 1.2, 3.0 and 9.0 Nm due to opening the actuators housing.
Opening the actuator’s housing will damage the actuator. The warranty expires.
NOTICE
The limits of the technical data must be strictly adhered to.
Function
662R5001...
662R5003...
662R5009...
Power supply
24 VDC ±20%
Floating time
5 s/90°
5 s/90°
15 s/90°
Direction of rotation 0° to 90°
left - view to the drive shaft
Effective
output torque
1.2 Nm (both directions of
rotation)
3 Nm (both directions of
rotation)
9 Nm (both directions
of rotation)
Holding torque
0.82 Nm (currentless)
2.8 Nm (currentless)
6 Nm (currentless)
Permissible radial load
100 N (centre of output shaft)
Permissible axial load
10 N
Axial play of drive shaft
0.1 ... 0.2 mm
(0.0039" x 0.0079" in)
0.1 ... 0.2 mm
(0.0039" x 0.0079" in)
0.1 ... 0.2 mm
(0.0039" x 0.0079" in)
Motor
RDM 51/6 stepper motor
Angular resolution
0.1°/motor step
0.1°/motor step
0.03°/motor step
Rated resolution
encoder monitoring
0,7°
Monitoring
accuracy
0,5°
0,5°
1.3125° (corre-
sponds 44 motor
steps)
Repeat accuracy
0,1°
0,1°
0,1°
Life cycle
2,000,000 motions forward and back performed on complete actuator range
Degree of protection
IP54 according to DIN EN 60529-1
Weight
1,400 g (3.09 lb)
Cable length
securely connected 1.5 m
(4.92 ft) pluggable max.
10 m (32.8 ft)
1
securely connected 1.5 m
(4.92 ft) pluggable max.
10 m (32.8 ft)*
pluggable max. 10 m
(32.8 ft)*
1 valid for appliances with SN1801... and higher
Environmental conditions 662R5001.../662R5003.../662R5009...
Operation
Climatic condition
Class 3K5 according to DIN EN 60721-3
Mechanical condition
Class 3M5 according to DIN EN 60721-3
Temperature range
-20 ... +60 °C (-4 ... +140 °F) (condensation is prohibited)
Transport
Climatic condition
Class 2K3 according to DIN EN 60721-3
Mechanical condition
Class 2M2 according to DIN EN 60721-3
Temperature range
-20 ... +70 °C (-4 ... +158 °F) (condensation is prohibited)
Storage
Climatic condition
Class 1K3 according to DIN EN 60721-3
Mechanical condition
Class 1M2 according to DIN EN 60721-3
Temperature range
-20 ... +70 °C (-4 ... +158 °F) (condensation is prohibited)
Bursting strength
Peak voltage
4 kV
Repeat frequency
2,5 kHz
Electrical safety
Protection class 2 as per DIN EN 60730
Summary of Contents for BT300 BurnerTronic
Page 2: ......
Page 25: ...24 3 Product Description Fig 3 9 Temperature derating BT300 for operation 2000 m NHN...
Page 49: ...48 4 Design and Functions Fig 4 20 Oil with pilot burner BT300...
Page 50: ...49 4 Design and Functions Fig 4 21 Oil without pilot burner BT300...
Page 51: ...50 4 Design and Functions Fig 4 22 Gas with pilot burner and leakage test BT300...
Page 52: ...51 4 Design and Functions Fig 4 23 Gas without pilot burner and leakage test BT300...
Page 53: ...52 4 Design and Functions Fig 4 24 Oil without pilot burner BT335...
Page 54: ...53 4 Design and Functions Fig 4 25 Gas without pilot burner and leakage test BT335...
Page 59: ...58 4 Design and Functions Fig 4 28 Leakage test process diagram...
Page 98: ...97 6 Operating Control and Displays...
Page 99: ...98 6 Operating Control and Displays...
Page 103: ...102 6 Operating Control and Displays...
Page 105: ...104 6 Operating Control and Displays...
Page 106: ...105 6 Operating Control and Displays...
Page 107: ...106 6 Operating Control and Displays...
Page 109: ...108 6 Operating Control and Displays...
Page 126: ...125 6 Operating Control and Displays 6 3 4 2 Curve Table Fig 6 37 Curve table window...
Page 246: ...242 10 EU Declaration of Conformity 10 EU Declaration of Conformity...
Page 247: ...243 10 EU Declaration of Conformity...