236
8
Options
8.5.4.7 Bit Encoding: State of Actual Value of O
2
Tab. 8-17 Bit encoding: Status of O
2
actual value
8.5.4.8 Bit Encoding: Cause of Faults of O
2
Trim
Tab. 8-18 Bit encoding: Cause of faults of O
2
trim
8.5.4.9 Bit Encoding: Operating Mode of CO Controller
Tab. 8-19 Bit encoding: CO controller mode
Status of O
2
Actual Value
Bit Pattern
HEX Code
Underflow
0000 0010 0000 0000
0x0200
Overflow
0000 0100 0000 0000
0x0400
Maintenance mode
0000 1000 0000 0000
0x0800
Sending replacement value
0001 0000 0000 0000
0x1000
Warning of the measurement value
0010 0000 0000 0000
0x2000
Failure of the measurement value
0100 0000 0000 0000
0x4000
Invalid measurement value
1000 0000 0000 0000
0x8000
Cause of error
Bit Pattern
HEX Code
Not enough O
2
during pre-purge
0000 0000 0000 0001
0x0001
Too much O
2
during pre-purge
0000 0000 0000 0010
0x0002
Too much O
2
after ignition
0000 0000 0000 0100
0x0004
Static fault of probe dynamics
0000 0000 0000 1000
0x0008
Invalid setpoint curve in operation
0000 0000 0001 0000
0x0010
Invalid optimisation curve in operation
0000 0000 0010 0000
0x0020
Exceeding 1
st
upper monitoring band
0000 0000 0100 0000
0x0040
Exceeding 1
st
lower monitoring band
0000 0000 1000 0000
0x0080
Half of the air deficiency is pending
0000 0001 0000 0000
0x0100
- -
0000 0010 0000 0000
0x0200
Invalid O
2
actual value
0000 0100 0000 0000
0x0400
The firing rate is outside the range for control
0000 1000 0000 0000
0x0800
Static air deficiency is pending
0001 0000 0000 0000
0x1000
Dynamic measures for counteractions are active in air
deficiency
0010 0000 0000 0000
0x2000
Probe dynamics is missing. Dynamic measures for coun-
teractions is active to create probe dynamics.
0100 0000 0000 0000
0x4000
The controller outputs a correction value of more than
970 digit for more than 1 h.
1000 0000 0000 0000
0x8000
CO Controller Operating Mode
Bit Pattern
HEX Code
CO controller is OFF.
0000 0000 0000 0000
0x0000
CO controller is released in the current curve set.
0000 0000 0000 0001
0x0001
CO controller is ready for controlling the correction.
0000 0000 0000 0010
0x0002
CO controller takes control over the correction while the burner is running.
0000 0000 0000 0100
0x0004
CO controller transfers the value for inactive correction because the O
2
trim may
not take control.
0000 0000 0000 1000
0x0008
Summary of Contents for BT300 BurnerTronic
Page 2: ......
Page 25: ...24 3 Product Description Fig 3 9 Temperature derating BT300 for operation 2000 m NHN...
Page 49: ...48 4 Design and Functions Fig 4 20 Oil with pilot burner BT300...
Page 50: ...49 4 Design and Functions Fig 4 21 Oil without pilot burner BT300...
Page 51: ...50 4 Design and Functions Fig 4 22 Gas with pilot burner and leakage test BT300...
Page 52: ...51 4 Design and Functions Fig 4 23 Gas without pilot burner and leakage test BT300...
Page 53: ...52 4 Design and Functions Fig 4 24 Oil without pilot burner BT335...
Page 54: ...53 4 Design and Functions Fig 4 25 Gas without pilot burner and leakage test BT335...
Page 59: ...58 4 Design and Functions Fig 4 28 Leakage test process diagram...
Page 98: ...97 6 Operating Control and Displays...
Page 99: ...98 6 Operating Control and Displays...
Page 103: ...102 6 Operating Control and Displays...
Page 105: ...104 6 Operating Control and Displays...
Page 106: ...105 6 Operating Control and Displays...
Page 107: ...106 6 Operating Control and Displays...
Page 109: ...108 6 Operating Control and Displays...
Page 126: ...125 6 Operating Control and Displays 6 3 4 2 Curve Table Fig 6 37 Curve table window...
Page 246: ...242 10 EU Declaration of Conformity 10 EU Declaration of Conformity...
Page 247: ...243 10 EU Declaration of Conformity...