34
6
Commissioning
6.3
Electrical Connection
NOTICE
It is not required to change to the respective mains frequency.
Periodic signals> 47 Hz are recognised for safety reasons as disorder. This covers the re-
quirements of standards for insensibility in the range of mains frequency (50/60 Hz) and their
multiples. Therefore it is not necessary to change the mains frequency on site.
You will find connection diagrams in the Appendix, Section
6.4
Putting the Device into Operation for the First Time
6.4.1
Requirements
Prerequisites for putting the device into operation for the first time:
•
The F300K must be mounted as specified in Section
•
The F300K must be aligned as specified in Section
•
All electrical installations must have been tested.
•
All terminal and plug-in connections must have been tested.
NOTICE
Putting the device into operation
To operate the F300K safely, you have to adhere to the following sequence when putting
it into operation for the first time:
1
Release access level 1 or 2 by means of a password: Section
.
2
Set the flame parameters of the F300K: Section
6.4.4 Setting Monitoring Parameters
3
Set the monitoring parameters of the F300K: Section
6.4.4 Setting Monitoring Parame-
.
4
Check the setting of the parameters by means of the switch-off test: Section
.
6.4.2
Parameter
During operation it is possible to change parameters. Parameters have a well-defined 2-digit
numbering and in most cases they are characterised by a symbol.
There are different sorts of parameters:
•
Operating mode parameters for the behaviour of flame detections
•
Device parameters of the flame scanner (p.ex. BUS-ID or current loop)
•
Device parameters of the User Interface (p.ex. light ON time)