Operation
7.5.3
Resetting the factory settings (up load)
WARNING!
Checking the switch-off parameters
There is a risk of death and serious injury.
The preset switch-off parameters are to be verified through switch-off tests, (see Section
). The change of the trigger threshold, the gain of the weighting (UV/
IR) and/or the frequency setting affects the switch-off parameters and therefore requires
renewed switch-off test.
Data (UI) to be loaded from the user interface (in this
case factory parameters for the active mode and the
safety time of FFDT 1 second)
Data (line 1) – loaded from user interface
Data (line 2) – received from the F300K
The data in line 1 must match the data in line 2.
A countdown of 8 seconds begins. This is accompa-
nied by flashing. During this countdown, you have to
confirm the setting by pressing
. If you do not, an
error message appears and the setting is rejected
The transfer was successful.