7   Internal Burner Firing Rate Controller

7

Internal Burner Firing Rate Controller

7.1

Purpose

The internal firing rate controller calculates the burner firing rate against a pre-defined setpoint 

value (e.g. as a function of temperature or pressure) by comparison with the actual value. This 

position will be transferred to the electronic fuel/air ratio control as a default value.

7.2

Moving Screen "Actual Temperature is too high"

7.3

Changing Setpoint of Burner-Firing-Rate Controller

see chapter 

7.5 How to Change the Burner-Firing-Rate Controller with the Customer Interface

7.4

Burner-Firing-Rate specified by hand

It is also possible to switch the FA1 to "Manual Control" with the terminals. By short-circuiting 

the Pt100 signal (e.g. bridge terminal 19 and 20) the burner firing rate controller is switched 

off. The fuel/air ratio controller then directly follows the input at the default firing rate input. The 

display shows LE instead of HA.

NOTICE

Only use manual control while monitoring the system.

7.5

How to Change the Burner-Firing-Rate Controller with the Customer Interface

Keep pressing the HAND key for more than 5sec., to switch the customer interface to the 

mode „set setpoints of burner firing rate controller“. This is only possible when burner firing 

rate controller is activated. At the same time, the HAND mode for manual firing rate input ends.
In the mode „setting firing rate controller“ the LED in the manual-key flashes. The lower display 

line shows the output regulator adjustment, the setpoint value and the actual value.

Active constant controller:

The Gerät can be started nevertheless by pressing the manual mode key provided that 

the maximum temperature is not exceeded.   

By pressing the manual mode key once more you switch to AUTO mode.

Press key MANUAL to move the regular firing rate input of the firing rate controller.
Press the keys 2 and 3 to variegate the burner firing rate.
Press key MANUAL again to cancel firing rate controller.

Press the key for 5 s long. Display = actual setpoint 1 or  2. 

This depends on the choice of setpoint values of terminal 50:

Terminal 50 = 0 V = setpoint value 1

Terminal 50 = 24 V = setpoint value 2

Summary of Contents for FA1

Page 1: ...www lamtec de Sensors and Systems for Combustion Engineering Quick Reference for Endusers Burner Control FA1...

Page 2: ......

Page 3: ...e Operating Unit 10 5 2 Connecting the Burner Control FA1 10 6 Fault 11 6 1 Reading Faults 11 6 2 Recalling Fault History 11 6 3 Resetting Faults 11 7 Internal Burner Firing Rate Controller 12 7 1 Pur...

Page 4: ...regulations DIN EN 298 2012 11 DIN EN 1643 2014 09 DIN EN 13611 2011 12 DIN EN 60730 2 5 2015 10 DIN EN 60730 1 2012 10 2014 35 EU Low Voltage Directive 2014 30 EU EMC Directive 2014 68 EU Pressure E...

Page 5: ...ility of imminent danger If it is not avoided it may result in death or very serious injury The plant including its surroundings could be damaged CAUTION This draws the user s attention to the possibi...

Page 6: ...1 continuously monitors its own functions and those of the connected control elements 230 V outputs actuation of the gas valves actuation of the oil valves actuation of the oil pump rotary atomiser ac...

Page 7: ...ime is based on the endurance tests specified in standard EN230 EN298 and the table containing the relevant test documentation as published by the European Association of Component Manufacturers Afeco...

Page 8: ...Fuel air ratio control O2 Flame intensity Operating hours Fig 4 2 Display with external burner firing rate controller Fig 4 3 Display in automatic mode Fig 4 4 Display in manual mode 70 setpoint of f...

Page 9: ...y after 5 s Fault of the O2 controller which lasts longer than 30 s would be saved After an idle time of 3 seconds provided that there is no operation of the keys within this time the display shows a...

Page 10: ...ET key effects as follows Leaving the 2nd display level in the lower display line Status report in the upper display line Disable manual mode Deactivate mode set burner firing rate controller Display...

Page 11: ...a 9 pin Cannon connector To do so use the supplied connecting cable type 663R0430 Data transmission takes place by the LAMTEC SYSTEM BUS 2 Alternatively Connect the operating unit with the cable of t...

Page 12: ...ponding operating hours counter value In initial state not MANUAL mode provided that no fault message of the FA1 is pending the upper display line is switching over 6 3 Resetting Faults NOTICE This ma...

Page 13: ...rol while monitoring the system 7 5 How to Change the Burner Firing Rate Controller with the Customer Interface Keep pressing the HAND key for more than 5sec to switch the customer interface to the mo...

Page 14: ...N TROLLER mode Press the key for 5 s long Display actual setpoint 1 or 2 and actual value This depends on the choice of setpoint values of terminal 50 Terminal 50 0 V setpoint value 1 Terminal 50 24 V...

Page 15: ...ng at both customer interfaces the shift key for a long time or one customer interfaces is disconnected temporarily Keep pressed the SHIFT key for a long time One after the other is shown CRC 16 of le...

Page 16: ...TING GL BASE FIRING RATE EG SETTING BASE FIRING RATE as BASIC FIRING RATE but FA1 on SETTING NA POST PURGE AU BURNER OFF no signal present EL SETTING SL CLEAR MEMORY EV SETTING PRE PURGE as PRE PURGE...

Page 17: ...to IEC 60127 2 Sheet 5 1500A 250VAC melting integral I t 40 A s e g Littelfuse 0215002 M XP Fuses which fulfills these requirements are ceramic tube fuses with the label T2AH 250V Fig 8 3 Rear view F...

Page 18: ...17 8 Appendix 8 3 EU Declaration of Conformity...

Page 19: ...18 8 Appendix...

Page 20: ...19 8 Appendix...

Page 21: ...20 8 Appendix...

Page 22: ...Co KG Wiesenstra e 6 D 69190 Walldorf Telefon 49 0 6227 6052 0 Telefax 49 0 6227 6052 57 info lamtec de www lamtec de Print no DLT6702 20 aEN 003 The information in this publication is subject to tech...

Reviews: