31
5
Firing Rate Controller (optional)
Fig. 5-6 Controller operation with I-term too high
Fig. 5-7 Controller operation with D-term too high
I term smaller
increase of attenu-
ation
less reaction, less ten-
dency to oscillate
slower start-up
Characteristic
Control Process
Control Mode
Start-up Procedure
D term higher
decrease of atten-
uation
stronger reaction
slower start-up, earlier
decrease of power
D term smaller
increase of attenu-
ation
less reaction
faster start-up,
decrease of power
later
Characteristic
Control Process
Control Mode
Start-up Procedure
Summary of Contents for VMS 4
Page 2: ......
Page 119: ...118 10 Appendix...
Page 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Page 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Page 142: ...141 10 Appendix...
Page 143: ...142 10 Appendix 10 15 Protocol Example...
Page 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Page 145: ...144 10 Appendix...