43
6
Commissioning
6.5.11
Change Curve Point
NOTICE
The separate ignition point can also be started up and changed in this way.
Turn selector switch (2) to SETTINGS
Turn selector switch (1) to LOAD RATING (firing rate)
Using switch (4) channel 1, run to firing rate of the
setpoints which are to be changed. Recognisable by
flashing digits after firing rate, e.g. 700 (8)
The display must show a digit or ’Z’ after the firing rate,
otherwise the VMS does not accept the change and a
point may be accidentally added.
Turn selector switch (1) to SETPOINT
Switch (4) up or down until system is optimally adjusted
at the selected firing rate.
VMS 5: Turn selector switch (1) to DISPLAY CHANNEL
5
the display shows setpoint and actual feedback
Switch (4) channel 2 up or down until channel 5 is opti-
mally adjusted.
Turn selector switch (1) to ACTUAL VALUE FEED-
BACK
Wait until feedback has stopped.
Press ENTER (3)
Point X (number of the new firing rate) appears on
the display
if necessary change another curve point
otherwise Save
Check monitoring values
Summary of Contents for VMS 4
Page 2: ......
Page 119: ...118 10 Appendix...
Page 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Page 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Page 142: ...141 10 Appendix...
Page 143: ...142 10 Appendix 10 15 Protocol Example...
Page 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Page 145: ...144 10 Appendix...