102
8
System Operation
Fault
Code
No.
Restart according to
Description
TRD
EN676
616
1
1
Ignition flame goes out in standby operation
617
1
1
Continuous ignition flame goes out under operation
618
0
0
Oil circulation: Temperature does not rise up within 45 sec.
620
0
0
Oil lance blow out: Delay for opening not kept
621
0
0
Oil lance blow out: Oil valve actuator not in ignition position
622
0
0
Oil lance blow out: blow out period too long
623
0
0
Atomizer switch-ON-pre-period not kept
624
>88
3
Oil pressure too low
625
>88
3
Oil pressure too high
626
>88
3
Atomizer air pressure too low
627
>88
3
General safety chain missing
700
0
0
Pre-ventilating signal present, without signal on terminal 2.
H
VMS, for ETA V Term. 58
701
0
0
Flame signal present, without signal on terminal 2.
H
VMS, for ETA V Term. 58
702
0
0
Flame signal appears during pre-ventilating.
H
VMS, for ETA V Term. 58
703
0
0
Flame signal goes out even though signal on terminal 2 still present.
H
VMS, for ETA V Term. 58
711
0
0
Illegal operating mode change
Ü
Check the "Burner ON" signal.
Bouncing signal?
712
0
0
713
0
0
Incorrect signal combination in operating mode AU
Ü
714
0
0
Incorrect signal combination in operating mode BE
Ü
715
0
0
Incorrect signal combination in operating mode VO
Ü
716
0
0
Incorrect signal combination in operating mode ZP
Ü
717
0
0
Incorrect signal combination in operating mode ZU
718
0
0
719
0
0
Fuel valves open too long without flame
Ü
720
0
0
Ignition transformer switched on too long
Ü
721
0
0
Ignition valve open too long
Ü
722
0
0
Fuel valves open in maintenance mode
Ü
723
0
0
Ignition process taking too long
Ü
Summary of Contents for VMS Series
Page 2: ......
Page 119: ...118 10 Appendix...
Page 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Page 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Page 142: ...141 10 Appendix...
Page 143: ...142 10 Appendix 10 15 Protocol Example...
Page 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Page 145: ...144 10 Appendix...