41
6
Commissioning
6.5.9
Check Monitoring Values
Turn selector switch (2) to MONITORING DISPLAY
–
The display switches to the values of the monitoring section
Turn selector switch (1) to FIRING RATE RATING (firing rate)
Move to programmed firing-rate rating
Turn selector switch to SETPOINT or ACTUAL VALUE FEEDBACK
NOTICE
The monitoring values may clearly deviate from the values of the main processor, depending
on the configuration (redundant signals or not). It is essential that the actual value matches
the setpoint value of the respective processors, not the correspondance of values between
the processors.
NOTICE
Should there be any redundant feedbacks, the curves must be programmed on a burner dur-
ing operation.
Summary of Contents for VMS Series
Page 2: ......
Page 119: ...118 10 Appendix...
Page 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Page 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Page 142: ...141 10 Appendix...
Page 143: ...142 10 Appendix 10 15 Protocol Example...
Page 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Page 145: ...144 10 Appendix...