44
6
Commissioning
6.6
O
2
Trim
6.6.1
Automatic Function Monitoring During Operation
6.6.1.1 Adjusted The Integrated O2 Controller (Optional)
This section explains only the operating steps needed to input the O
2
curve. Further informa-
tion on O
2
controller is contained in the publication DLT 5002 Commissioning Supplement for
the Optional ’Integrated O
2
Controller’.
6.6.1.2 Test During Burner Start
The actual O
2
value is checked to ensure that during pre-purge it corresponds to the air value
(equal to or greater than 18 vol.% O
2
and less than 24 vol.% O
2
).
After ignition, the actual O
2
value must reach a value equal to or below 14% within 45 seconds.
Reaching the threshold value is monitored. If one of the two parameters is not met, O
2
trim is
deactivated. The control unit outputs the value “Base value without control”.
6.6.1.3 O
2
Monitoring Band
During burner operation, the actual O
2
value is continuously monitored for one maximum and
two minimum permissible values. These ranges are located around the O
2
setpoint as a func-
tion of firing rate. If the actual values stay outside these bands for a defined period, the control
system is deactivated and a “Fault” warning is output.
Thereafter, the control unit’s output (correction input) corresponds to “Base value without con-
trol” or “Base value with air deficiency”.
Summary of Contents for VMS Series
Page 2: ......
Page 119: ...118 10 Appendix...
Page 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Page 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Page 142: ...141 10 Appendix...
Page 143: ...142 10 Appendix 10 15 Protocol Example...
Page 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Page 145: ...144 10 Appendix...