81
8
System Operation
NOTICE
This mode allows the electronic fuel/air ratio control to run within curve sections already en-
tered and thereby facilitates setting.
If the firing rate drops by 40 points, the VMS skips to ES mode, thereby controlling the outputs
automatically.
ES mode is also started if the switch 1 is set to FIRING RATE and the channel 2 switch is
pushed up.
Back to normal programming
Tap on a switch
the VMS changes to EI mode
Continue programming in the usual way
8.1.4
Proceed with Programming
If the burner is omitted due to control shutoff, proceed as follows:
Undertake no further action on the VMS
Wait until the boiler temperature has fallen
Allow burner to start normally
Pre-purge.
the display shows EV
VMS control the outputs according to the pre-purge
Burner ignites
ES appears on the display
VMS controls the output according to the entered sub curve
NOTICE
The highest firing rate already entered would not be exceeded.
WARNING!
For your safety:
ES mode should be run only by trained personnel with the system under constant supervision.
Run to next firing-rate to be programmed
Push switch up
VMS switch back to EL mode
continue programming at the point where the burner cut-out previously occurred
NOTICE
Should the mains voltage to the Gerät has failed (display dark, operating LEDs out), before
switching back to AUTOMATIC, all curve points already entered will have been lost. Start pro-
gramming from beginning again.
Summary of Contents for VMS Series
Page 2: ......
Page 119: ...118 10 Appendix...
Page 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Page 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Page 142: ...141 10 Appendix...
Page 143: ...142 10 Appendix 10 15 Protocol Example...
Page 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Page 145: ...144 10 Appendix...