12
Call 1-888-370-6531 for Technical Support
5.3 Safety Systems and Warnings
Several systems built into the burner controls ensure that the burner operates safely and will
shut down if something is wrong:
Fuel Preheater Control:
This device prevents the oil from being overheated by the preheater
in the nozzle block assembly. The preheater will heat up the fuel to the target temp (default:
140
o
F) then it cuts power to the heaters until the oil starts to cool down. If starting from
completely cold (power has been off), allow at least 10 minutes for the oil to heat up before
turning on the thermostat and trying to light the burner.
Cad Cell:
The flame-sensing “cad cell’ detects the light emitted by the flame to determine that
the flame is on. On a call for heat from the thermostat, if the burner does not light within 30
seconds, or if the flame goes out for any reason, the controller will shut down the burner. This
prevents the accumulation of unburned fuel in the combustion chamber, potentially generating
smoke, rumbling and/or misfiring once the burner lights.
Primary Control – Recycle Mode:
Once a flame has been established, if the burner loses
flame for any reason, the Primary Control will shut off the burner and enter Recycle Mode.
After approximately 60 seconds, the Primary Control will attempt to restart the burner. If no
flame is seen by the cad cell during the restart attempt, the Primary Control will lock out until
it is manually reset. To reset, press and hold the red reset button on the primary control. If
the cad cell sees a flame, the Primary Control will continue running the burner until the call
for heat is satisfied.
Multiple resets may allow fuel to accumulate in the heat exchanger, therefore
do not reset more than one or two times without diagnosing the issue. Contact Technical
Support for assistance.
DO NOT ATTEMPT TO START THE BURNER WHEN EXCESS FUEL
HAS ACCUMULATED IN THE CHAMBER, WHEN THE HEATER IS FULL OF
VAPOR, OR WHEN THE COMBUSTION CHAMBER IS VERY HOT. Refer to section
6.4.1 (heat exchanger cleaning) for instructions on removal of excess fuel.
Summary of Contents for MX 75
Page 2: ......
Page 41: ...8 Appendices 8 1 Wiring Diagram ...
Page 42: ......
Page 43: ...34 Call 1 888 370 6531 for Technical Support 8 2 Primary Control Instructions ...
Page 44: ...35 Call 1 888 370 6531 for Technical Support Not used with RES 75 kBTU h units ...
Page 45: ...36 Call 1 888 370 6531 for Technical Support No latch up with RES 75 kBTU h units ...
Page 46: ...37 Call 1 888 370 6531 for Technical Support ...
Page 54: ...45 Call 1 888 370 6531 for Technical Support 9 ...