General Requirements
1.
Do not install the heater on a combustible surface of any kind. For minimum clearance to
combustible material (see Page 1).
2.
Install the heater in a location to utilize total heat throw (blown hot air).
3.
Install the heater in a location to permit a correct outdoor chimney exit to eliminate down
drafts, and provide easy chimney installation and maintenance. Class A chimney MUST be
used when passing through any wall or ceiling. See Section 4 Chimney Installation.
4.
Install the heater in a location to permit the fuel supply to be as close as possible.
5.
If the heater is not installed on a tank stand supplied by Lanair, a metering pump may be
desired in order to eliminate the need to adjust oil flow from a distance.
6.
Before suspending the heater check the supporting structure and reinforce if necessary to
support the weight of the heater/system.
7.
Use 3/8”, 16 TPI, steel threaded rod and locking nuts to suspend the heater from a capable
load carrying ceiling structure when not mounting to a Lanair Waste Oil Storage Tank.
8.
The heater must be suspended level for proper operation. A heater that is not level could
cause a hazardous situation in which personal injury or property damage may result.
Adjustable Locking Louvers
The XT Series heaters feature spring
loaded locking louvers. To adjust:
•
Slowly push the louver to the left
until the locking pin disengages.
NOTE
: Do not allow the pivot pin
to come out of the hole.
•
Tilt the louver forward/backward
until desired position is obtained.
•
Release louver so locking pin
seats into the hole.