background image

7

Adjust Water Flow Rate & Syrup/Water Ratio

 

The refridgeration unit should have been running for at 

least one (1) hour before attempting to set flow rates 

 

on valves. The drink temperature should be no higher 

than 40°F (4.4°C) when flow rates are set. This is best 

done after the unit has already made an ice bank.

NOTE

1.  Set the three (3) way back block to dispense plain water or 

carbonated water, depending on the type of syrup installed 

on the previous page, for each valve.  

2.  Close syrup shut-off at mounting block for first valve. 
3.  Using a Lancer brix cup verify water flow rate (5 oz. in 4 

sec.). Use a screwdriver to adjust if needed.

4.  Remove nozzle by twisting counter clockwise and pulling 

down, then remove diffuser by pulling down.

5.  Install Lancer (yellow) syrup separator 

(PN 54-0031)

 in place 

of nozzle.

A

B

Increase

Decrease

C

E

A. Flow Control, Water

B. Flow Control, Syrup

C. Nozzle (Diffuser inside)

D. Mounting Block (not shown)

E. Soda Lever

D

A

B

C

A. Syrup Separator

B. Nozzle

C. Soda Lever

6.  Re-open syrup shut-off at mounting block.
7.  Activate valve to purge syrup until steady flow is achieved.
8.  Using a Lancer brix cup, activte the valve and capture a 

sample. Verify that the syrup level is even with the water 

level. Use a screwdriver to adjust if needed. 

A

B

A. Plain Water ON     

B. Syrup Closed

9.  Repeat process for each valve. 
10.  Re-install the merchandiser, splash plate, cup rest, and drip 

tray then reattach bonnet using the top bonnet screw.

A

B

C

A. Syrup Separator

B. Brix Cup

C. Verify Soda/

    Water Level

Volumetric Valve Adjustment

 

The Volumetric Valve is an optional valve for the 

 

CED-06 dispenser

NOTE

1.  Remove the ID panel from the front of the first valve. 
2.  Insert the programmer’s 10-pin connector into the ID panel 

plug located on the front of the circuit board.

3.  When properly connected, the programmer will run a self  

diagnostic test. The display will show all “8’s” with the          

decimal points lighted. After about three (3) seconds, the 

display indicates the setting of the dip switches.

 

If the programmer does not run its diagnostic test

 

properly, disconnect it and try plugging it in again. If

 

the programmer still fails, replace the programmer

NOTE

4.  After the programmer is connected, Press the “Read Mem” 

button.

5.  Press the “Ratio +” or the “Ratio -” key until the desired ratio 

is displayed.

6.  Verify the drink type by pressing “Carb Toggle” to select “C” 

for carbonated or “n” for non-carbonated.

7.  Press the “Enter” button to program the valve with the setting 

on the display.

8.  Verify Ratio by pressing “Read Mem”.
9.  Disconnect the programmer and repeat steps 4-9 for each 

valve. 

- Handheld Programmer 

Volumetric Valve

Summary of Contents for DELTA6 Series

Page 1: ...to the dispenser lies with the carrier The installation and relocation if necessary of this product must be carried out by qualified personnel with up to date safety and hygiene knowledge and practica...

Page 2: ...63 0 kg Operating 219 lbs 99 3 kg CARBON DIOXIDE CO2 SUPPLY Min Pressure 70 PSIG 0 483 MPA Max Pressure 80 PSIG 0 552 MPA FITTINGS Carbonator Inlet 3 8 inch barb Plain Water Inlet 3 8 inch barb Brand...

Page 3: ...e compressor to overheat and will result in compressor failure ATTENTION Selecting Preparing Counter Location The dispenser should only be installed in a location where it can be overseen by trained p...

Page 4: ...mp location to the syrup inlets located behind the splash plate Connect tubing to inlets using the oetiker pliers and fittings Repeat for all syrup connections If the unit being installed has built in...

Page 5: ...riate tubing from the syrup pump syrup supply location to the CO2 inlet and connect tubing to CO2 inlet If the water source is above 50 PSIG 0 345 MPA cut tubing assembly and install Water Regulator K...

Page 6: ...Carbonated Water Setup 1 Purge water to fill carbonator tank by opening carbonator relief valve Close relief valve once water comes out A Relief Valve Open B CO2 Inlet C CO2 Line A B C 2 Activate each...

Page 7: ...he water level Use a screwdriver to adjust if needed A B A Plain Water ON B Syrup Closed 9 Repeat process for each valve 10 Re install the merchandiser splash plate cup rest and drip tray then reattac...

Page 8: ...110 F 32 C to 43 C The mixture ratio is one ounce of cleaner to two gallons of water Prepare a minimum of five gallons of cleaning solution Do not use abrasive cleaners or solvents because they can ca...

Page 9: ...reates a health hazard CAUTION Cleaning and Sanitizing Nozzles 1 Disconnect power so as to not activate valve while cleaning 2 Remove nozzle by twisting counter clockwise and pulling down 3 Remove dif...

Page 10: ...10 WIRING DIAGRAM 115 V 60 Hz R744 WIRING DIAGRAM 230 V 50 Hz 220 V 60 Hz R744...

Page 11: ...M 115 V 60 Hz 230 V 50 Hz 220 V 60 Hz R134A PLUMBING DIAGRAM PLAIN WATER COILS CARB HIGH PRESSURE WATER PUMP V6 V5 V4 V3 V2 V1 S1 PW1 S2 S3 S4 S5 S6 PLAIN WATER INLET TO CARBONATOR PLUMBING DIAGRAM CE...

Page 12: ...Lancer Corp 800 729 1500 Technical Support Warranty 800 729 1550 custserv lancercorp com lancercorp com...

Reviews: