(Section 4.15 continued from previous page.)
C. Inadequate voltage.
C. Measure voltage across common
and run terminal on compressor.
Voltage must not drop below 90%
of rated voltage.
D. Incorrect wiring.
D. Refer to wiring diagram and correct.
E. Defective condenser fan motor. E. Replace condenser fan motor.
F. Refrigerant leak.
F. Repair and recharge.
G. Compressor malfunctioning.
G. Replace compressor.
4.16 Compressor and
A. Transformer tripped.
A. Reset transformer.
Condenser Fan Motor
B. Relay will not turn on
B. Failed relay. Replace Control
will not start after
compressor.
Board.
five (5) minute Power
C. Probe unplugged.
C. Check probe connection at PCB.
Off delay
(Lancer EIBC
Export only)
.
4.17 Compressor and
A. Improper Wiring.
A. Check Power Indicator Lamp;
Condenser Fan Motor
check wiring per Wiring Diagram.
will not start after
B. Probe unplugged.
B. Check Probe connection at PCB.
five (5) minute Power
C. Damaged electronics.
C. Replace Control.
Off delay
(Lancer EIBC,
USA Only)
.
4.18 Warm drinks.
A. Restricted airflow.
A. Check clearances around sides,
top, and inlet of unit. Remove
objects blocking airflow through
grill.
B. Dispenser connected to hot
B. Switch to cold water supply.
water supply.
C. Refrigeration system not
C. Refer to Sections 4.11 - 4.16.
running.
D. Refrigerant leak.
D. Repair and recharge.
E. Condenser fan motor not
E. Replace condenser fan motor.
working.
F. Dirty condenser.
F. Clean condenser.
G. Dispenser capacity exceeded. G. Add pre-cooler.
NOTES
7
TROUBLE
CAUSE
REMEDY