Siberian Elite Glycol Chiller 220V / 60Hz
www.lancerbeverage.com
Page 12 of 17
Hoshizaki Lancer reserve the right to change specifications without notice
Part No: 68000205
Images are for illustration purposes only as product may vary.
No 016
– 12 February 2016
8. Trouble Shooting
TROUBLE
CAUSE
REMEDY
Condensing unit will
not start.
Power Failure
Pumps not active
Thermostat probe failure
Solenoid coil failure
Check for blown circuit breaker or
cord pulled out.
Replace
Replace solenoid
Beer Warm
Glycol bath temp outside control
set points
Suction line hand valve(if fitted) is
closed
Faulty glycol pump
Faulty TX valve
Incorrect glycol concentration
(poor agitation)
Check set points
Open hand valve
Replace pump
Replace TX valve
Check with refractometer & adjust
No product flow
Thermostat set too low
Frozen product line
Adjust set point
Switch off refrigeration while leaving
pumps running & allow thawing.
Some beers will freeze when set
temp below 28
0
f
Noise evident
Noisy pump
Replace/repair pump
No glycol flow
Frozen HX plate
Low glycol level
Low glycol %
Adjust set point
System leak
Add glycol