6. Thermostat
– Carel Pjeasy – Thermostat
Parameters
NOTE:
The Thermostat will not be energised unless the refrigeration switch is turned on.
6.1
Thermostat Settings
Parameter
Type
Def
Description
St
Set point
28
Refrigeration will turn off when glycol reaches this temperature.
rd
F
2.0
Temperature differential, glycol temperature will increase from the
cut out point by this value before the refrigeration turns on.
AF
F
23
Antifreeze alarm set point. If the evaporator suction line reaches this
temperature the control will stop the refrigeration system and will
require a manual reset.
Antifreeze alarm can be reset by holding “UP” and “DOWN” keys for
5 seconds.
In case of probe 2 failure, the antifreeze alarm function is inhibited
and regulation is still performed.
If “AF parameter is set to its minimum value the alarm function is
inhibited.
rt
F
**
Time (in hours) of max/min temperatures logging.
rH
F
**
Highest/ maximum recorded temperature.
rL
F
**
Lowest/ minimum recorded temperature.
AH
F
36.0
High temperature alarm (relative to set point).
AL
F
7.2
Low temperature alarm (relative to set point).
c2
F
3 mins
Minimum time in mins after turning off before the control will give an
output to the refrigeration solenoid (short cycle protection).
r4
F
13.0
Value to increase the set point in ECO mode.
r2
F
41
Maximum allowed set point.
r1
F
23
Minimum allowed set point.
Controls programmed during manufacture.
All other non used parameters are hidden to avoid confusion.