background image

3

INSTALLATION

Unpack the Dispenser

1. 

Set shipping carton upright on the floor then cut package 

banding straps and remove.

2.  Open top of carton and remove interior packaging. 
3. 

Lift carton up and off of the unit.

4.  Remove plywood shipping base from unit by moving unit so 

that one side is off the counter top or table allowing access 

to screws on the bottom of the plywood shipping base.

6.  If leg kit has been provided, assemble legs by tilting unit.

 

If unit is to be transported, it is advisable to leave the 

unit secured to the plywood shipping base.

 

NOTE

 

Inspect unit for concealed damage. If evident, notify 

 

delivering carrier and file a claim against the same.

NOTE

5.  Remove accessory kit and loose parts from ice compartment.

Selecting/Preparing Counter Location

1.  Select a level, well ventilated location that is in close 

proximity to a properly grounded electrical outlet, within five 

(5) feet (1.5 m) of a drain, a water supply that meets the 

requirements shown in the Specifications section found on 

page 2, and away from direct sunlight or overhead lighting. 

2. 

Sufficient clearance must be provided, if an ice maker is not 

installed, to allow filling ice compartment from a five gallon 

bucket (a minimum of 16 inches is recommended). 

3.  The selected location should be able to support the weight of 

the dispenser, ice and possibly an icemaker being installed 

after counter cut out is made. Total weight (with icemaker) for 

this unit could exceed 800 pounds (363.6kg).

 

Lancer does 

NOT

 recommend the use of shaved or

 

flake ice in the dispenser.

NOTE

4. 

Unit may be installed directly on counter-top or on legs. If 

installed directly on the counter, unit must be sealed to the 

countertop with an FDA approved sealant. If an icemaker is 

to be mounted on top of dispenser, do not install dispenser 

on legs. 

5.  Select a location for the remote pump deck, syrup pumps, 

CO

2

 tank, syrup containers, and water filter (recommended).                                                                                  

6.  Cut out required opening for the water, syrup, and CO

2

 lines 

in the designated dispenser location.

 

In order to facilitate proper dispenser drainage, ensure 

that the dispenser is level, front to back and side to 

side. Place a level on the top of the rear edge of the 

 

dispenser. The bubble must settle between the level 

lines. Repeat this procedure for the remaining three 

sides. Level unit if necessary. For optimum perfor-

mance place the unit at a 0° tilt. The maximum tilt is 5°.

Leveling the Dispenser:

 

NSF listed units must be sealed to the counter or use 

legs provided.

NOTE

 

To assure that beverage service is accessible to all 

customers, Lancer recommends that counter height 

and equipment selection be planned carefully. The 

2010 ADA Standards for Accessible Design states that 

the maximum reach height from the floor should be no 

more than 48” if touch point is less than 10” from the 

front of the counter, or a maximum of 46” if the touch 

point is more than 10” and less than 27” from the front 

of the counter. For more information about the 

 

customer’s legal requirements for the accessibility of 

installed equipment, refer to 2010 ADA Standards for 

Accessible Design - http://www.ada.gov.

NOTE

Installing an Icemaker (if necessary)

When installing an icemaker on the dispenser, use a 

bin thermostat to control the ice level (see below). This 

will prevent damage to the dispensing mechanism. The 

bracket for mounting a thermostat is located in the ice 

bin. During the automatic agitation cycle and while    

dispensing ice, ensure there is adequate space be-

tween the top of the ice level and the bottom of the 

icemaker so the ice can move without obstruction. 

Contact your icemaker manufacturer for information  

on a suitable bin thermostat.

ATTENTION

1. 

Install the icemaker per manufacturer specifications. Points 

of consideration include drainage, ventilation, and drop 

zones.

2.  An adapter plate is required when installing an icemaker. 

Contact your Sales Representative or Lancer Customer 

Service for more information.

3.  A bin thermostat is required in order to control the level of ice 

in the dispenser (Refer to ATTENTION above). Contact your 

icemaker manufacturer to obtain the correct bin thermostat. 

4.  Bin thermostat should be a minimum of 2” below the top 

edge of the dispenser. The preferred location of the bin   

thermostat is on the left side wall. 

4”

Attach Bin Stat Bracket As Shown

Recommended Bin Stat Attachment

Bulb

Tube

Summary of Contents for Twin Pour

Page 1: ...ss or for your convenience scan this QR code with a mobile device app required for immediate access to other Technical Documents and alternative translations if available pertaining to this unit Conta...

Page 2: ...ing 585 lbs 265 kg Operating w Ice 745 lbs 338 kg Ice Capacity 312 lbs 142 kg CARBON DIOXIDE CO2 SUPPLY Min Pressure 70 psi 0 483 MPa Max Pressure 80 psi 0 552 MPa FITTINGS Carbonator Inlet 3 8 inch b...

Page 3: ...re that the dispenser is level front to back and side to side Place a level on the top of the rear edge of the dispenser The bubble must settle between the level lines Repeat this procedure for the re...

Page 4: ...n a counterclockwise direction up to a 45 angle 4 Carefully pull ADA panel and electric wire harness from the unit s splash plate until the harness connector is visible 5 Disconnect ADA harness and re...

Page 5: ...Tube to become clogged with coffee or tea grounds or other solid particles ATTENTION 16 Reattach Drip Tray and Cup Rest to unit if applicable When installing the drip tray make sure both of the cold p...

Page 6: ...nut on the regulator adjustment screw of the high pressure CO2 regulator connected to the source then using a screwdriver back out lock nut screw all the way DO NOT TURN ON CO2 SUPPLY AT THIS TIME WA...

Page 7: ...d right screen by pressing the screen on off toggle buttons on the left side of the unit electrical box The manager s access to the service menu allows access to the Lighting screen see page 12 the So...

Page 8: ...flipping the switch on the control box NOTE To check for CO2 leaks close the valve on the CO2 cylinder and observe if the pressure to the system drops with the cylinder valve closed for five minutes O...

Page 9: ...Repeat Steps 4 and 5 for any of the other brand or flavor modules 8 Press the Menu button to return to the Service menu 12 Press the Menu button to return to the Service Menu 13 Repeat steps 1 12 for...

Page 10: ...m on page 17 for reference 1 From the Service menu press the Maintenance button 2 Remove the two thumb screws connecting the plastic screen housing to the unit See page 9 3 While holding the plastic s...

Page 11: ...9 for the remaining brand syrup modules 11 To re attach the screen housing first align the screen housing with the connection tabs on the unit then rotate the housing down untill the connection tabs...

Page 12: ...sing down untill the connection tabs engage 13 Re connect the two thumb screws removed in Step 2 14 Repeat steps 1 13 for the second screen Make sure both of the connection tabs are disengaged in the...

Page 13: ...problem with the specified brand and will dispense when activated Auto signifies that the configured Sold Out Sensor controls whether the brand can be dispensed This feature requires an optional sold...

Page 14: ...ble water at a temperature of 90 F to 110 F Extended lengths of product lines may require additional cleaning solution Sanitizing Solution Prepare the sanitizing solution in accordance with the manufa...

Page 15: ...twenty 20 seconds ensuring all surfaces of the nozzle have been thoroughly rinsed 9 Allow outer nozzle to air dry to expedite drying forced convection is recommended 10 Reinstall the outer nozzle to t...

Page 16: ...ll interior surfaces of the ice chute and the ice chute feed through 29 Wearing sanitary gloves reassemble all removable parts Ensure agitator clip is locked 30 Fill unit with ice and replace Top Cove...

Page 17: ...ement Residual sanitizing solution left in the system creates a health hazard CAUTION 7 Flush out cleaning solution from the flavor injector lines using clean warm water 8 Prepare Sanitizing Solution...

Page 18: ...ED 3 5a C B 3 5a C B 7A C B CONTROL PCB R CONTROL PCB L ICE SOLE ICE SOLE TRIGGER TRIGGER 12VDC 12VDC 24VDC 24VDC 24VDC 115VAC 24VDC 24VDC HDMI HDMI USB USB USB USB CTRL PCB CTRL PCB LEFT SIDE VALVES...

Page 19: ...Blk Red WHT N N N L N G V V V V GRN WHT BLK WHT BLK GRN GRN BLK WHT RED BLK RED WHT BLK WHT BLK BLK WHT WHT BLK BLK RED RED BLK GRN WHT BLK POWER SUPPLY AND IBD CONTROLLER BOX 2 to 1 adapter RIGHT RI...

Page 20: ...6 7 6 2 2 3 8 3 4 7 4 5 SW1 SWITCH 1 NOT USED FOR MODEL 4900 ON 5 4 SWITCH AGITATOR ON TIME 5 6 OFF OFF 11 SECONDS OFF ON 9 SECONDS ON OFF 7 SECONDS ON ON 5 SECONDS SWITCH AUGER RUN TIME 7 8 OFF OFF 6...

Reviews: