Installation
11/21
4.1 Installation for cooling metering
Note:
The local regulations (installation etc.) must be adhered to.
When installing as a cooling meter it is essential that the black cover on the
measuring tube is pointed to the side or down-wards in order to avoid prob-
lems with condensation. Fit the immersion sleeves so that the temperature
sensor is positioned vertically downwards or horizontally.
Note:
Always install the volume measurement unit on the hot side.
Fit the electronic unit separate to the volume measurement tube, e.g. on the
wall. Make a loop downwards in order to prevent condensation running along
the connected lines into the electronic unit.
Transducer cover
Fig. 9: Recommended installation position for cooling metering