8
INSTALLATION
DANGER:
THIS APPLIANCE MUST BE GROUNDED AT THE
TERMINAL PROVIDED. FAILURE TO GROUND THE
APPLIANCE COULD RESULT IN ELECTROCUTION AND
DEATH.
WARNING:
INSTALLATION OF THE UNIT MUST BE DONE BY
PERSONNEL QUALIFIED TO WORK WITH ELECTRICITY.
IMPROPER INSTALLATION CAN CAUSE INJURY TO
PERSONNEL AND/OR DAMAGE TO EQUIPMENT. UNIT
MUST BE INSTALLED IN ACCORDANCE WITH ALL
APPLICABLE CODES.
NOTICE:
The data plate is located on the back of each griddle. The
griddle voltage, wattage, serial number, wire size and
clearance specifications are on the data plate. This
information should be carefully read and understood
before proceeding with the installation.
NOTICE:
The installation of any components such as a vent hood,
grease extractors and/or fire extinguisher systems must
conform to their applicable National, State and locally
recognized installation standards.
Electrical Connection
Follow the receptacle manufacturer’s instructions when connecting the receptacle
to the power supply.
The electrical connection must be made in accordance with local codes or in the
absence of local codes with NFPA No. 70 latest edition (in Canada use: CSA STD.
C22.1).
The electrical service entrance is provided by a cord and plug located at the rear of
the appliance.
The plug provided for 208/240V is a L6-30P. The PBE12 120V comes with a
standard plug. The receptacle for a 208/240V is a L6-30R and must be supplied by
the installer. The PBE12 120V will use a standard receptacle.
Supply wire size must be large enough to carry the amperage load for the number
of appliances being installed. Wire size information can be found on the data plate.