background image

 
 

 

 

29 

Langer & Laumann Ingenieurbüro GmbH       48356 Nordwalde      Wallgraben 30      

+49 (02573) 9 55 99 0        

                                                                                                                                            

http://www.LuL-Ing.de

 

+49 (02573) 9 55 99 5        Email: Info@LuL-Ing.de

Langer & Laumann 

 

I n g e n i e u r b ü r o            G m b H

Geschäftsführer

Dipl.- Ing.  Michael  Laumann
Dipl.- Ing.  Matthias Langer

 

/ Managing Director

Bankverbindung 
Sparkasse Steinfurt    

/ Bank Account

  

BLZ: 40351220  Kto: 7024631

  WELADED1STF   

 De52 4035 1060 0007 0246 31

BLZ: 40061238  Kto: 8623333000

 GEBODEM1GRV   

 De66 4006 1238 8623 3330 00

BIC

IBAN

Volksbank Greven EG  
BIC

IBAN

Handelsregister 
Amtsgericht Steinfurt HRB 2943
Ust.-Id.Nr.

De195553428

Steuer-Nr. 311 5870 1056

/ Comercial Register

 / Vat-No. 

8.3 Stop input 

 
The TSG electronic board has a separate input for stop. If the connection on terminal strip X5 between 

terminals 1 and 2 is opened, the motor is stopped (electronic brake applied). 

 appears in the display. 

After the connection is restored, the TSG door control device resumes normal operation.  
 
In normal operation, there is a wire bridge present between X5.1 and X5.2.  
 

 

CAUTION:

  

No external voltage may be connected to terminals X5.1 and/or X5.2. Doing so will cause 
irreparable damage to the TSG electronic board and may result in uncontrolled door 
movements! 
 

 

 

WARNING: 

The stop function does not correspond to the requirements of Standard EN954 and is 
therefore not subject to any safety category! The function must not be used in safety-relevant 
control applications! 
 

 
 
 
 
 
 
 

8.4  Restart after power failure and restoration of mains power 

 
After a power failure, when power is restored, the TSG door control unit searches for the programmed end 
position at the speed set by parameter h6. If parameter h7 is utilized the door control unit will search for the 
second position at the speed is set in parameter h7. 
 
 

CAUTION:

 

Please ensure that the path of the door is free from obstruction during the referencing journey 
after power failure. 
 
 

 

 

Summary of Contents for TSG 200

Page 1: ...Dipl Ing Matthias Langer Managing Director Bankverbindung Sparkasse Steinfurt Bank Account BLZ 40351220 Kto 7024631 WELADED1STF De52 4035 1060 0007 0246 31 BLZ 40061238 Kto 8623333000 GEBODEM1GRV De66...

Page 2: ...protection these operating instructions may not be copied in whole or in part without written approval of Langer Laumann Ingenieurb ro GmbH except as part of normal use of the product or to create a b...

Page 3: ...________________________ 17 6 3 User setting P parameters ______________________________________________________ 17 7 Advanced parameters ____________________________________________________________ 1...

Page 4: ...r Dipl Ing Michael Laumann Dipl Ing Matthias Langer Managing Director Bankverbindung Sparkasse Steinfurt Bank Account BLZ 40351220 Kto 7024631 WELADED1STF De52 4035 1060 0007 0246 31 BLZ 40061238 Kto...

Page 5: ...he TSG door operator from hardware version 3 4 and software version 4 26 onwards Only by following these instructions will you Avoid mistakes Avoid damaging the equipement Safely install the TSG door...

Page 6: ...or personal injury or property damage Any other or more extensive use is considered contrary to designated use and may result in personal injury for the user or third parties as well as damage to prop...

Page 7: ...control and operation of the TSG door control device Unqualified personnel are prohibited from working on the TSG door control device Personnel must have knowledge of first aid measures and on site r...

Page 8: ...e mechanisms engage in each other in the closed position CAUTION When positioning and commissioning the TSG door control device in or on an elevator car make certain the total permissible weight of th...

Page 9: ...door opening width is determined by a measurement process The range of service applications for the TSG door control unit is divided into the following groups 1 TSG 200 up to about 180 200 kg door pa...

Page 10: ...avel path of the door Springs and or dampers that were required for previous door drives must be removed when installing the TSG door control device 4 2 Installation process 1 Mount the TSG drive It d...

Page 11: ...aring Fig 1 TSG toothed belt tension At and axle distance of a 1 m axle centre centre deflection should be e 16 mm and force should be F 18 5 N CAUTION A TSG toothed belt tension that is too low may r...

Page 12: ...icht Steinfurt HRB 2943 Ust Id Nr De195553428 Steuer Nr 311 5870 1056 Comercial Register Vat No 5 Electrical settings and commissioning 5 1 Display The TSG electronics unit has a two digit 7 segment d...

Page 13: ...egister Vat No 5 2 Menu structure There is a jog wheel on the TSG electronics unit for operating and adjusting the TSG door controller between the 7 segment display and the relay outputs Press the jog...

Page 14: ...rip X4 and the shield terminal of the TSG motor cable to X8 on the TSG electronics board Plug the TSG encoder cable into terminal strip X3 sub D9 plug 4 Turn on the supply 230 VAC mains 5 Select param...

Page 15: ...n procedure Parameter EE is used to reset parameters to their default values see also Table 6 E parameters page 25 5 4 Manual mode manual travel To select Manual mode choose parameter P1 The display a...

Page 16: ...52 4035 1060 0007 0246 31 BLZ 40061238 Kto 8623333000 GEBODEM1GRV De66 4006 1238 8623 3330 00 BIC IBAN Volksbank Greven EG BIC IBAN Handelsregister Amtsgericht Steinfurt HRB 2943 Ust Id Nr De195553428...

Page 17: ...lockwise c c w reduces the menu To see the values of the relevant parameter press the jog wheel briefly Table 2 P parameters Function Note Default Min Max Factor Unit P0 Return to special functions P1...

Page 18: ...246 31 BLZ 40061238 Kto 8623333000 GEBODEM1GRV De66 4006 1238 8623 3330 00 BIC IBAN Volksbank Greven EG BIC IBAN Handelsregister Amtsgericht Steinfurt HRB 2943 Ust Id Nr De195553428 Steuer Nr 311 5870...

Page 19: ...ally change some of the C parameter values see also Fig 6 Open door curve with c parameter or Fig 7 Close door curve with c parameter page 18 7 2 1 User setting c parameters The c parameters can be se...

Page 20: ...e in Open direction with input signal Open door 0 0 1 0 3 0 A cF Holding torque in Close direction with input signal Close door 0 0 1 0 3 0 A CC Exit the menu Select CC and press the jog wheel to leav...

Page 21: ...on of Obstructed detection in Open direction oF Off on On oF on on b6 Suppression of Obstructed detection in the first 30 of the Open distance oF Off on On oF On on b7 Limit value of Obstructed detect...

Page 22: ...ry set to 01 by default This parameter must not be changed without consulting with the technical department of Langer Laumann 00 01 05 CC Exit the menu Select CC and press the jog wheel to leave the b...

Page 23: ...is not lit open the door at slow speed for the next run 00 00 03 h4 Switching delay of door is open output relay With this parameter a delay distance of switching of the door is open output relay can...

Page 24: ...tor Unit hb Closing and opening time of the skate Only with additional board that can be optionally fitted and hA 01 or hA 03 0 1 0 7 3 0 seconds hC Pause between opening of the skate and opening of t...

Page 25: ...imum number of times that the controller can count these errors The errors E1 to Ed are not adjustable Table 6 E parameters Parameter Function Min Default Max Factor Unit E0 Travel not limited 00 00 9...

Page 26: ...the current motor current r3 Operating voltage of end stage VDC Shows the current voltage on the end stage r4 Mains power voltage VAC Shows the current mains power voltage Note the display shows the l...

Page 27: ...u parameters Parameter Function Note Min Defau lt Max Factor Unit A0 Intermediate position 1 Only with additional board that can be optionally fitted oF oF on oF Off on On A1 Intermediate position 2 O...

Page 28: ...egister Vat No 8 TSG connections 8 1 X1 inputs The inputs for signals Open door X1 1 Close door X1 2 and reserved X1 3 can be wired with a voltage of 24 VDC AC see also Table 13 X1 inputs page 44 CAUT...

Page 29: ...the display After the connection is restored the TSG door control device resumes normal operation In normal operation there is a wire bridge present between X5 1 and X5 2 CAUTION No external voltage m...

Page 30: ...se this allowable static force The kinetic energy produced by the doors is a product of the weight of the lift doors and the set speed of the TSG door operator Parameters P2 P3 P4 Refer to the informa...

Page 31: ...off and on with parameter bE If parameter b4 on the door is automatically reversed when it is obstructed After it reaches the Open position the door closes again If parameter b3 on the obstructed rel...

Page 32: ...rol device a holding torque can be set so that the door will be held in place Holding torque parameter in Closed position without signal Open door cC Holding torque parameter in Open position without...

Page 33: ...not defined Check the mechanic of the door Toothed belt failed Check the toothed belt E1 Door travel path locked The door does not move This error occurs outside the range of Obstructed detection With...

Page 34: ...coder damaged Replace the incremental encoder cable Incremental encoder damaged Replace the drive E5 The target actual values do not match Wrong voltage Check power supply Incremental encoder damaged...

Page 35: ...he mechanics are changed at the same time a new initial measurement movement must be started EF Delete error counters All error counters will be deleted If detection is turned off for E6 see parameter...

Page 36: ...8 Kto 8623333000 GEBODEM1GRV De66 4006 1238 8623 3330 00 BIC IBAN Volksbank Greven EG BIC IBAN Handelsregister Amtsgericht Steinfurt HRB 2943 Ust Id Nr De195553428 Steuer Nr 311 5870 1056 Comercial Re...

Page 37: ...g Director Bankverbindung Sparkasse Steinfurt Bank Account BLZ 40351220 Kto 7024631 WELADED1STF De52 4035 1060 0007 0246 31 BLZ 40061238 Kto 8623333000 GEBODEM1GRV De66 4006 1238 8623 3330 00 BIC IBAN...

Page 38: ...sse Steinfurt Bank Account BLZ 40351220 Kto 7024631 WELADED1STF De52 4035 1060 0007 0246 31 BLZ 40061238 Kto 8623333000 GEBODEM1GRV De66 4006 1238 8623 3330 00 BIC IBAN Volksbank Greven EG BIC IBAN Ha...

Page 39: ...ng on uneven surfaces Fig 14 TSG hat combination bracket Fig 15 TSG hat combination dimensions NOTE Special arrangements and support brackets are possible please contact Langer Laumann to discuss your...

Page 40: ...Emergency power supply The TSG electronics unit is optionally available with an emergency power supply The emergency power supply consists of an additional electronic part on the TSG board and two ba...

Page 41: ...he elevator control system or directly to the TSG control board If the light curtain is directly attached to the TSG control board input X1 3 parameter h3 must be configured accordingly The signal fro...

Page 42: ...aintenance work that the drive cannot be turned on and that no electrical voltages can accidentally be applied to exposed parts After these measures are complete safety and protective equipment on the...

Page 43: ...BIC IBAN Handelsregister Amtsgericht Steinfurt HRB 2943 Ust Id Nr De195553428 Steuer Nr 311 5870 1056 Comercial Register Vat No 15 Technical data for TSG electronics 15 1 Overview of TSG electronics...

Page 44: ...sition about 5 W Storage temperature 0 C 60 C Ambient operating temperature 10 C 40 C no direct sunlight X1 inputs 15 24 VDC AC X2 relay outputs switching capacity 24 V 4 A 230 V 1 A Note If relays or...

Page 45: ...is Open output common X2 2 Door is Open output n c normally closed contact X2 3 Door is Open output n o normally open contact X2 4 Door is Closed output common X2 5 Door is Closed output n c normally...

Page 46: ...9 pin SubD 1 free 2 free 3 free 4 free 5 free 6 Inc negative Cable wire motor version K Yellow Cable wire motor version D Brown motor side 1 7 Inc track B Cable wire motor version K Green Cable wire m...

Page 47: ...WELADED1STF De52 4035 1060 0007 0246 31 BLZ 40061238 Kto 8623333000 GEBODEM1GRV De66 4006 1238 8623 3330 00 BIC IBAN Volksbank Greven EG BIC IBAN Handelsregister Amtsgericht Steinfurt HRB 2943 Ust Id...

Page 48: ...pl Ing Michael Laumann Dipl Ing Matthias Langer Managing Director Bankverbindung Sparkasse Steinfurt Bank Account BLZ 40351220 Kto 7024631 WELADED1STF De52 4035 1060 0007 0246 31 BLZ 40061238 Kto 8623...

Page 49: ...Bankverbindung Sparkasse Steinfurt Bank Account BLZ 40351220 Kto 7024631 WELADED1STF De52 4035 1060 0007 0246 31 BLZ 40061238 Kto 8623333000 GEBODEM1GRV De66 4006 1238 8623 3330 00 BIC IBAN Volksbank...

Reviews: