Fault/Error Function
Meaning
Cause
Remedy
E3 Obstructed
for
reversing
The door drive has
detected an
obstruction and
reversed itself. The
door was Obstructed
during reversing.
There is an
obstruction in the
door.
Check the travel path.
(see also E1)
E4
No signal from the
encoder
Cable to the
incremental encoder
damaged.
Replace the
incremental encoder
cable.
Incremental encoder
damaged.
Replace the drive.
E5
The target / actual
values do not match.
Wrong voltage
Check power supply.
Incremental encoder
damaged.
Replace the drive.
E6
Encoder error
No values can be sent
from the incremental
encoder (on the motor)
to the TSG.
Incremental encoder
damaged.
Replace the drive.
Cable to the
incremental encoder
damaged.
Replace the
incremental encoder
cable.
Blade-type fuse SI3
tripped.
Eliminate the cause for
blade-type fuse SI3
being tripped and
replace the fuse.
Motor line faulty or
not plugged in.
Check motor line and
plug.
End stage faulty.
Replace TSG
electronics unit.
E7 Obstructed
after
switching on again
Door was Obstructed
after power was
restored.
Check the travel path. (see also E1)
E8 Mains
power
start-
ups
Counter for the
number of mains
power start-ups.
Mains power voltage
failure. The device will
perform a restart.
Check the supply line.
Check the back-up
fuse.
Check the fuse on the
TSG electronics unit.
Replace TSG
electronics unit.
Ed Motor
recognition
error
Incorrect door motor
is connected to the
TSG controller.
Replace motor.