Grounding the Chassis 

The ION002-AD chassis comes equipped with grounding lugs located on its back panel. They require a grounding 

conductor wire terminated with a two-hole, compression-type, grounding connector (not provided). The grounding 

wire (must be a copper conductor) is not included with the chassis and must be provided by the 

customer/installer. 
The electrical-conducting path from the ION002-AD chassis must: 

  Flow via the grounding lugs to the common bonding network (CBN) for telecom installations, or to an 

alternative approved grounding system (if required) for non-telecom installations. 

  Be of sufficiently low impedance to conduct fault currents likely to be imposed on the media converter. 

  Enable proper operation of any over-current protection devices. 

Grounding Wire Size 

The wire size of the Protective Earth (ground) conductor should be greater than or equal to the wire size of the 

power source conductors. The power-source conductor wire size is installation dependent and sized to 

accommodate acceptable IR losses between the power source and the device terminal block. The device terminal 

block accommodates #6 wire lugs. A #6 wire lug typically terminates #16 - #20 wire; with #18 most common. 

Connecting the Ground Wire 

The conductor must be fastened to the grounding lugs with the enclosed antirotation star-washers and lug-nut 

fasteners. The torque requirement for the connector lug-nut fasteners is specified by the connector’s 

manufacturer. 

Grounding Methods 

The conductor must be fastened to the grounding lugs with the enclosed antirotation star-washers and lug-nut 

fasteners. The torque requirement for the connector lug-nut fasteners is specified by the connector’s 

manufacturer. 
To properly ground the ION002-AD chassis: 
1.  Obtain one (1) a two-hole, compression-type, grounding connector. 

2.  Attach the grounding conductor to the chassis by placing the two-hole connector onto the grounding lugs and 

fasten with the enclosed lockwashers/lug-nuts at the proper torque (per the manufacturer’s specification). 

3.  Attach the opposite end of the grounding conductor to the common-bonding network (CBN) for telecom, or to 

earth ground (if required) for non-telecom installations. 

 

   

 

 

 

 

Summary of Contents for ION002-AD

Page 1: ...ION 2 Slot Chassis ION002 AD User Guide Part Number 33612 Revision B February 2022...

Page 2: ...t Sales Offices For a current list of our domestic and international sales offices please go to www lantronix com about contact Disclaimer All information contained herein is provided AS IS Lantronix...

Page 3: ...lide In Cards 6 Powering the Chassis 7 Power via the DC INPUT EuroBlock Connector 7 Grounding the Chassis 9 Grounding Wire Size 9 Connecting the Ground Wire 9 Grounding Methods 9 Dimensions 10 Mountin...

Page 4: ...ION002 AD 2 Slot ION Chassis desktop with AC or DC power input Options The ION002 AD options listed below are sold separately Model Description WMBP Optional Wall Mount Bracket 5 0 in 127 mm WMBV Opti...

Page 5: ...3573 3 ION x4110 Web User Guide 33574 or CLI Reference 33575 4 ION Management Module IONMM Install Guide 33420 and User Guide 33457 5 ION System NID User Guides 33432 33457 33472 33493 33494 33495 334...

Page 6: ...and observe electrostatic discharge precautions when installing slide in cards into the dual slot chassis Failure to observe this caution could result in damage to the slide in cards Note The maximum...

Page 7: ...erminal block is 21 60 VDC polarity insensitive This terminal block can be used if your installation site offers a low voltage DC power source See Power via the DC INPUT EuroBlock Connector below for...

Page 8: ...the Terminal Block note p olarity on the ION002 AD chassis Make sure the wires are secure See figure below 3 Insert the positive and negative power wires into V and V contacts respectively into the po...

Page 9: ...is installation dependent and sized to accommodate acceptable IR losses between the power source and the device terminal block The device terminal block accommodates 6 wire lugs A 6 wire lug typicall...

Page 10: ...al Vertical Mount Bracket 5 0 in 127 mm For More Information See the related slide in card manuals for information on Pre Installation DIP Switch settings Installation and Setup Installing slide in ca...

Page 11: ...e in card lit NO Is the slide in card properly seated Is the power adapter the proper type and cycle frequency for the AC outlet See technical specifications Is the power adapter properly installed in...

Page 12: ...rking This is a Class A product In a domestic environment this product could cause radio interference as a result the customer may be required to take adequate preventative measures UL Listed Power Su...

Page 13: ...pean Parliament and of the Council of 27 January 2003 Lantronix will accept post usage returns of this product for proper disposal The contact information for this activity can be found in the Contact...

Page 14: ...rden ge nstalleerd S curit lectrique IMPORTANT Cet quipement doit tre utilis conform ment aux instructions de s curit S hk turvallisuus T RKE T m laite on asennettava turvaohjeiden mukaisesti Sicurezz...

Page 15: ...covery Suite 250 Irvine CA 92618 USA Toll Free 800 526 8766 Phone 949 453 3990 Fax 949 453 3995 Technical Support Online https www lantronix com technical support Sales Offices For a current list of o...

Reviews: