06: Bypass enable/disable when UPS is off
Interface Setting
Parameter 3:
Enable or disable Bypass function. You may
choose the following two options:
ENA:
Bypass enable
DIS:
Bypass disable
z
07: Bypass voltage range setting
Interface Setting
Parameter 2 & 3:
Set the acceptable high voltage point and
acceptable low voltage point for Bypass mode by pressing the
Down key or Up key.
HLS:
Bypass high voltage point
For 208/220/230/240 VAC models:
230-264:
setting the high voltage point in parameter 3 from
230Vac to 264Vac.
For 110/115/120/127 VAC models:
120-132:
setting the high voltage point in parameter 3 from
120Vac to 132Vac
LLS:
Bypass low voltage point
For 208/220/230/240 VAC models:
170-220:
setting the low voltage point in parameter 3 from
170Vac to 220Vac
For 110/115/120/127 VAC models:
85-115:
setting the low voltage point in parameter 3 from 85Vac
to 115Vac.
z
08: Programmable outlets enable/disable
Interface Setting
Parameter 3:
Enable or disable programmable outlets.
ENA:
Programmable outlets enable
DIS:
Progr
ammable outlets disable
z
09: Programmable outlets setting
Interface Setting
Parameter 3:
Set up backup time limits for programmable
outlets.
0-999:
setting the backup time limits in minutes from 0-999 for
programmable outlets which connect to non-critical devices on
battery mode.
z
00: Exit setting