background image

 

LA-GL-ON-LCD 

 

2. Installation and setup 

NOTE: 

Before installation, please inspect the unit. Be sure that nothing inside the package is 

damaged. Please keep the original package in a safe place for future use. 

NOTE:

 There are two different types of online UPS: standard and long-run models. Please 

refer to the following model table. 
 

Model Type 

Model 

Type 

1K 1K-L 
2K 2K-L 
3K 

Standard 

3K-L 

Long-run 

 

2.1. Rear panel view 

   1K(L) TOWER 

 

 

    2K(L) TOWER 

 

 

    3K(L) TOWER 

 

 

 

 

 

 

 

 

1K(L) RACK 

2K(L) RACK

 

3K(L) RACK

 

 

 

 

 

1.  Programmable outlets: connect to non-critical loads.   

2.  Output receptacles: connect to mission-critical loads. 

3. AC input 

4.  Input circuit breaker 

5. Network/Fax/Modem surge protection 

6.  Emergency power off function connector (EPO) 

7.  USB communication port 

8.  RS-232 communication port 

9.  SNMP intelligent slot 

10. External battery connection (only available for L model) 

11. Output  terminal 

12. Output circuit breaker 

 

Summary of Contents for LA-GL-ON-1K-LCD

Page 1: ...Online UPS 1K 2K 3K Uninterruptible Power Supply System USER MANUAL EN ...

Page 2: ...nd faults 3 2 Installation and setup 4 2 1 Rear panel view 4 2 2 Setup the UPS 5 3 Operations 7 3 1 Button operation 7 3 2 LCD Panel 7 3 3 Audible Alarm 9 3 4 LCD display wordings index 9 3 5 UPS Setting 9 3 6 Operating Mode Description 12 3 7 Faults Reference Code 12 3 8 Warning indicator 13 4 Troubleshooting 14 5 Storage and Maintenance 15 6 Specifications 16 ...

Page 3: ...ip over them z Do not connect domestic appliances such as hair dryers to UPS output sockets z The UPS can be operated by any individuals with no previous experience z Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system z Please use only VDE tested CE marked mains cable e g the mains cable of your computer to connect the UPS system...

Page 4: ...ons must be kept well away from the batteries z Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Before touching please verify that no voltage is present z Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures specified below a...

Page 5: ...del Type 1K 1K L 2K 2K L 3K Standard 3K L Long run 2 1 Rear panel view 1K L TOWER 2K L TOWER 3K L TOWER 1K L RACK 2K L RACK 3K L RACK 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC input 4 Input circuit breaker 5 Network Fax Modem surge protection 6 Emergency power off function connector EPO 7 USB communication port 8 RS 232 communi...

Page 6: ...low below steps for the wiring configuration a Remove the small cover of the terminal block b Suggest using AWG14 or 2 1mm2 power cords Suggest using WG12 10 or 3 3mm2 5 3mm2 power cords for NEMA type c Upon completion of the wiring configuration please check whether the wires are securely affixed d Put the small cover back to the rear panel Step 3 Communication connection Communication port USB p...

Page 7: ...ring software to fully configure UPS shutdown You may insert provided CD into CD ROM to install the monitoring software If not please follow steps below to download and install monitoring software from the internet 1 Go to the website http www power software download com 2 Click ViewPower software icon and then choose your required OS to download the software 3 Follow the on screen instructions to...

Page 8: ...ery mode UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage output voltage and output frequency It will return back ...

Page 9: ...y 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Programmable outlets information Indicates that programmable management outlets are working Mode operation information Indicates the UPS connects to the mains Indicates the battery is working Indicates the bypass circuit is working Indicates the ECO mode is enabled Indicates the Inverter circuit ...

Page 10: ...ndex Abbreviation Display content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss BAT Battery CF Converter EP EPO FA Fan TP Temperature CH Charger 3 5 UPS Setting There are three parameters to set up the UPS Parameter 1 It s for program alternatives There are 9 programs to set up Refer to below table Parameter 2 and parameter 3 are the setting options or values for each progra...

Page 11: ... 50 present output frequency is 50Hz BAT 60 present output frequency is 60Hz If converter mode is enabled you may choose the following output frequency CF 50 present output frequency is 50Hz CF 60 present output frequency is 60Hz z 04 ECO enable disable Interface Setting Parameter 3 Enable or disable ECO function You may choose the following two options ENA ECO mode enable DIS ECO mode disable z 0...

Page 12: ...20 132 setting the high voltage point in parameter 3 from 120Vac to 132Vac LLS Bypass low voltage point For 208 220 230 240 VAC models 170 220 setting the low voltage point in parameter 3 from 170Vac to 220Vac For 110 115 120 127 VAC models 85 115 setting the low voltage point in parameter 3 from 85Vac to 115Vac z 08 Programmable outlets enable disable Interface Setting Parameter 3 Enable or disab...

Page 13: ...e Battery mode When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 second UPS will backup power from battery Bypass mode When input voltage is within acceptable range but UPS is overload UPS will enter bypass mode or bypass mode can be set by front panel Alarm is sounding every 10 second Standby mode UPS is powered off and no output supply power but...

Page 14: ...very second Battery is not connected Sounding every second Over Charge Sounding every second Site wiring fault Sounding every second EPO enable Sounding every second Fan Failure Sounding every second Over temperature Sounding every second Charger failure Sounding every second Out of bypass voltage range Sounding every second ...

Page 15: ...y connected Check if all batteries are connected well Fault code is shown as 27 and the icon is lighting on LCD display and alarm is continuously sounding Battery voltage is too high or the charger is fault Contact your dealer Fault code is shown as 28 and the icon is lighting on LCD display and alarm is continuously sounding Battery voltage is too low or the charger is fault Contact your dealer U...

Page 16: ...er Battery backup time is shorter than nominal value Batteries defect Contact your dealer to replace the battery The icon and the warning code flashing on LCD display and alarm is sounding every second Fan is locked or not working Check fans and notify dealer 5 Storage and Maintenance Operation The UPS system contains no user serviceable parts If the battery service life 3 5 years at 25 C ambient ...

Page 17: ...tio 3 1 Harmonic Distortion 3 THD Linear Load 6 THD Non linear Load 4 THD Linear Load 7 THD Non linear Load AC Mode to Batt Mode Zero Transfer Time Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 85 88 Battery Mode 83 BATTERY Battery Type 12 V 7 AH 12 V 7 AH 12 V 9 AH Numbers 3 6 6 Recharge Time 4 hours recover to 90 capacity Typical Charging Current 1 0 A max S...