LA-ITR-LCD
4
2. Installation And Setup
NOTE:
Before installation, please inspect the unit. Be sure that nothing inside the package is
damaged. Please keep the original package in a safe place for future use.
2.1. Rear Panel View
LA-ITR-800-LCD
/ LA-ITR-1100-LCD /
LA-ITR-1500-LCD
/ LA-ITR-2000-LCD
LA-ITR-2500-LCD
/
LA-ITR-3000-LCD
/
1. Programmable outlets: connect to non-critical loads.
2. Output receptacles: connect to mission-critical loads.
3. AC input
4. Input circuit breaker
5. Network/Fax/Modem surge protection
6. Emergency power off function connector (EPO)
7. USB communication port
8. RS-232 communication port
9. SNMP intelligent slot
10. External battery connector (only available for L model)
11. External battery pack numbers detection port
2.2. Install the UPS
For safety consideration, the UPS is shipped out from factory without connecting battery wires.
Before install the UPS, please follow below steps to re-connect battery wires first.
Step 1
Step 2
Step 3
Remove front panel.
Connect the AC input and
re-connect battery wires.
Put the front panel back to the unit.