background image

   44428235 

ASSEMBLY INSTRUCTION

 

 

Valid from: 

17.07.2019

 

EPIC

®

 SOLAR 4 PLUS 

 

Document: L44428235EN 
Version: 02 

Page 4 of 9 

We reserve all rights according to DIN ISO 16016. 

Safety Instructions 

 
The Connector EPIC

®

 SOLAR 4 PLUS is not able to be connected or disconnected under load. 

De-energize the circuit by appropriate measures, e.g. at the inverter.  To disconnect and to 
connect without load, under voltage, is possible. 
EPIC

®

 SOLAR 4PLUS Connectors are intended to connect stationary photovoltaic systems. 

They are suitable for fixed installation in dry or damp rooms, as well as outdoors. EPIC

®

 SOLAR  

products are not suitable for laying into earth. 
PV Cables 
Designation   

 

 

LAPP KABEL H1Z2Z2-K 

Cable Code   

 

 

H1Z2Z2-K 

Rated cross-section :   

 

4,0 mm²; 6,0 mm²; 10,0 mm² 

Rated Voltage :  

 

 

AC U0/U 1,0/1,0 kV 

 

 

 

 

 

DC 1,5 kV 

max. Voltage :  

 

 

DC 1,8 kV (Conductor / Earth) 

 

 

 

 

 

System without Earth Connection 

 
Mated connectors are IP68 protected, 1m 10 h. A permanent use under water, e. g. water on 
the roof of a flat roof is not possible. 
 
EPIC

®

 SOLAR connectors shall be mounted only with tools and accessories specified by Lapp. 

The connection of the cable at the connector must be performed by qualified electricians.  To 
protect the installer from the danger of the electric current, the connector must be made 
floating on all sides during assembly. 
Unplugged connectors must be protected against ingress of dirt and moisture. Before plugging 
together, make sure that the mating area is free of any dirt. 

 
Note :The PV Connectors  EPIC

®

 SOLAR 4 Plus are not rewirable. 

 

Defective connectors can be replaced by new connectors of the same type and 
connection cross-section, complying with all requirements of this installation 
instruction and having ensured that the connector is without voltage and not under 
load. 

 

 

 

Summary of Contents for EPIC SOLAR 4Plus Series

Page 1: ...to DIN ISO 16016 EPIC SOLAR 4 PLUS ASSEMBLY INSTRUCTION Contents Scope of delivery 2 Contacts 2 Technical Specifications 3 Safety Instructions 4 Necessary Tools 5 Mounting of EPIC SOLAR 4 PLUS 6 Analy...

Page 2: ...PLUS is delivered pre assembled the necessary contacts are included separately EPIC SOLAR 4 Plus X Y Item number Designation 44428235 EPIC SOLAR 4 PLUS M 4 0 mm or 6 0 mm 44428236 EPIC SOLAR 4 PLUS F...

Page 3: ...014 Rated Voltage 1 500 V DC Rated Current 30 A 4 0mm 30 A 6 0mm 30 A 10 mm Rated impulse withstand voltage 16 kV Rated temperature 40 C 85 C Upper Limit of Temperature 105 C Protection degree IP68 10...

Page 4: ...DC 1 5 kV max Voltage DC 1 8 kV Conductor Earth System without Earth Connection Mated connectors are IP68 protected 1m 10 h A permanent use under water e g water on the roof of a flat roof is not pos...

Page 5: ...able LAPP Universal Strip Solar Item number 21920120 EPIC SOLAR Mounting Tool is not necessary Two 19 mm open end wrenches are enough Crimping Tool Note To comply the tested quality it s necessary to...

Page 6: ...male Connector field mountable including Contacts 44428236 EPIC SOLAR 4PLUS F 4 mm 6 mm 4 6 5 2 7 1 8 30 44428238 EPIC SOLAR 4PLUS F 10 mm 10 5 2 7 1 12 30 EPIC SOLAR 4PLUS Male Connector field mounta...

Page 7: ...pletely into the crimp area of the contact The cable is pushed forward until the insulation strikes the crimp receptacle of the contact In this way the supermatent is insured at least 2 mm Completely...

Page 8: ...erly engaged Turn cap nut hand tight 4 5 Nm finished Spanner size 19 EPIC SOLAR 4PLUS F Connecting and Disconnecting Before plugging in check the plug in area for any dirt and if necessary clean it Es...

Page 9: ...The cables must be laid firmly in the photovoltaic system securely fastened and the minimum bending radius shall not be undercut The cable shall be led out staight at least L 50 mm The bending radius...

Reviews: