background image

1.. DIRECTIONS FOR 

BOX 

IN

ST

ALLATION

1.

 Mount the back box by means of mounting lugs,

 

install conduit nipple and sealing fittings one each

 

to be

installed on each conduit entrance or exit

 

to the enclosure back box in Class l and Class ll

 

areas (Reference:

Article 500 NEC) thread conduit

 

into sealing fitting 

(Note: for Class l areas the

 

conduit should engage [5]

full threads).

2.

The conduit thread should be lubricated with a

 

non-electrical insulating lubricant or pipe joint

 

compound that

will not promote corrosion or

 

chemically attack aluminium.

3.

 After conduit system has been properly installed,

 

pull the wires and make electrical connections as

 

required.

The electrical circuits and ground

 

continuity should be checked with an instrument

 

approved for the area.

(Notice: connect only

 

copper wire to this device).

4.

 All conduits entering or leaving the enclosure

 

must be sealed within 18” of the enclosure with

 

listed sealing

fittings.

5.

 Caution must be taken during installation to be

 

sure that the ground flange flame joints of the

 

cover and the

box are not scratched, nicked or

 

damaged.

6.

 Before assembly of the cover to the box, the

 

mating ground surfaces of both the box and cover

 

should be

wiped clean to assure that the ground

 

flame joint will be free of all foreign particles such

 

as lint, dust or dirt.

7.

After tightly bolting the cover assembly/assemblies

 

to the enclosure all box to cover, flame joints

 

should be

checked with a 0.0015” thick feeler

 

gauge such that the gauge will not enter the flame

 

path more than 1/8” at

any point.

2.. MAINTENAN

CE

All moving shafts should be lubricated 

occasionally 

to prevent binding. Only use a lubricant which is 

suitable for use with aluminium or stainless steel such as general purpose or

 

high temperature lubricants. If 

devices are to be installed in corrosive areas 

which will attack aluminium alloys containing less 

than 0.4% 

copper (boxes and covers) and 303 stainless steel (mostly shafts), the device should be suitably protected 

from the corrosive material.

3.. CAUTI

ON

To prevent ignition of hazardous atmospheres, disconnect from the supply circuits before opening the 

enclosure; keep tightly closed while circuits are energized.

BOX IDENTIFICATION

IDENT

NO.

NO

GANGS

IDENT.

NO

NO

GANGS

7

2

21

5

8

2

30

4

9

2

32

6

10

2

33

8

11

2

34

10

12

2

35

6

17

2

36

9

18

2

37

12

19

3

38

15

20

4

EPCS-PL-2X-RG

Larson Electronics, LLC

 

Fax: (903) 498-3364 

www.larsonelectronics.com 

3

 of 

3

 

THESE INSTRUCTIONS MAY  NOT COVER ALL DETAILS OR VARIATIONS OF THIS PRODUCT FOR YOUR EQUIPMENT OR INSTALLATION REQUIREMENTS. 
SHOULD FURTHER INFORMATION NOT COVERED BY THESE INSTRUCTIONS BE REQUIRED, PLEASE CONTACT LARSON ELECTRONICS BY EMAIL AT 

SALES@LARSONELECTRONICS.COM

 OR BY PHONE AT 1-800-369-6671 FOR FURTHER ASSISTANCE. 

PLEASE VISIT LARSONELECTRONICS.COM FOR 

WARRANTY

 AND 

RETURN

 INFORMATION.

 Phone: 

877-348-9680

 

Reviews: