C1D1 Explosion Proof High Bay LED Fixture w/ Emergency Battery
Backup - Paint Spray Booth Approved
Instruction Manual
This explosion proof light is designed for illumination of industrial locations. It uses the latest in
solid state lighting technology for long life, low maintenance and high efficiency.
The unique design focuses the light where it is needed, giving improved efficiency over a
conventional HID luminaire.
This light fixture is shipped preconfigured to work in the selected voltage range. This includes 100-
277V AC 50/60hz or 11-25V AC/DC depending on model selected. An internal, universal input power-
factor-corrected switch allows it to be used from any voltage within range without variation in light
output.
Check product label for correct input voltage!
WARNING
To avoid the risk of fire, explosion or electric shock, this product should be installed, inspected
and maintained by a qualified electrician only, in accordance with all applicable electrical codes.
To avoid electric shock:
Be certain electrical power is OFF before and during installation and maintenance.
Luminaire must be connected to a wiring system with an equipment-grounding conductor.
To avoid explosion:
Make sure the supply voltage is within the luminair
es’ voltage rating.
Ensure the marked T rating is less than the ignition temperature of the Hazardous
Atmosphere.
Do not operate in ambient temperatures above those indicated on the luminaire nameplate.
Do not operate if the lens is cracked or damaged. All fasteners should be properly seated.
For supply connections, use wire rated for at least 110°C
Recommended mounting height is 15-40 feet.
MOUNTING
The EPL-EMG-HB-50LED-RT-WLM offers a flat surface mounting system, mounted with four bolts
through the tabs on the wiring junction box. This mounting feature caters to wall mounting
preferences.
WIRING
(see
below
wiring diagram)
The EPL-EMG-HB-50LED-RT-WLM explosion proof wall mount LED light fixture is equipped with 10
feet of abrasion and chemical resistant 16/3 SOOW cable with flying leads. The LED light fixture
features 5 3/4" NPT threaded ports for running conduit; four of the ports are located on the corners of
the unit and the fifth port is found on the rear of the explosion proof wall mount LED fixture.
Feed
wiring through a port to complete connections.
1.
(See wire diagram)
Wire the “Neutral”, “Hot”, and “Ground”
wires to power source.
2.
Wire White/Red to switch if applicable.
WARNING:
CHECK NAMEPLATE
FOR PROPER VOLTAGE. DAMAGE
FROM IMPROPER VOLTAGE WILL
VOID WARRANTY.