EPL-SW Series

 

Explosion Proof Tumbler Switch

Class I, II, III - Copper-free Aluminum - NEMA

Instruction Manual

Thank you for your purchase of the Larson Electronics 

EPL-SW Series Explosion Proof switch. 

WARNING 

TO AVOID THE RISK OF FIRE, EXPLOSION OR ELECTRIC SHOCK, THIS PRODUCT SHOULD BE INSTALLED, 

INSPECTED AND MAINTAINED BY A QUALIFIED ELECTRICIAN ONLY, IN ACCORDANCE WITH ALL 

APPLICABLE ELECTRICAL CODES. 

TO AVOID ELECTRIC SHOCK: 

BE CERTAIN ELECTRICAL POWER IS OFF BEFORE AND DURING INSTALLATION AND MAINTENANCE.

PRODUCT  MUST  BE  CONNECTED TO A  WIRING  SYSTEM  WITH  AN  EQUIPMENT-GROUNDING

CONDUCTOR.  

TO AVOID EXPLOSION: 

MAKE SURE THE SUPPLY VOLTAGE IS WITHIN THE VOLTAGE RATING.

ENSURE THE MARKED T RATING IS LESS THAN THE IGNITION TEMPERATURE OF THE HAZARDOUS

 

ATMOSPHERE.

DO NOT OPERATE IN AMBIENT TEMPERATURES ABOVE THOSE INDICATED ON  THE PRODUCT

 

NAMEPLATE.

DO NOT OPERATE IF THE  LENS, CORD, SEALS, HOUSING, RECEPTACLES, ETC. IS CRACKED OR

 

DAMAGED. IF SO, DISCONTINUE USE AND CONTACT MANUFACTURER FOR REPLACEMENT PARTS.

ALL FASTENERS SHOULD BE PROPERLY SEATED.

WARNING:

 

To avoid risk of explosion

, all flat machined surfaces must be kept clean and free from scratches, 

dents, debris, paint, and corrosion. The flat machined surfaces are explosion proof joints, and must be clean and 

undamaged on both the enclosure and cover. 

The Larson Electronics EPL-SW Explosion Proof Tumbler Switch provides a safe and secure method for operators to 

interrupt power before connecting and disconnecting electrical equipment in hazardous locations. This 20-amp device is 

compatible with single-phase 120-277V AC and features lever style switch(es). Available in single and double gang box 

configuration.

Larson Electronics, LLC

 

Phone: (877) 348-9680

 Fax: (903) 498-3364 

  www.larsonelectronics.com 

1

 of 

2

 

Mounting

 and Installation

Mounting of the EPL-SW is achieved via mounting tabs on the back of the 

enclosure. Mount to a clean, flat surface with customer provided mounting 

hardware. Hardware is not included with this switch, but is available from Larson 

Electronics. Contact Larson Electronics if you wish to order. 

1. 

The surfaces of the flat ground joint are precision machined to insure an 

explosion proof joint and must be protected from scratches or damage during 

installation.

2. 

When switch is mounted in the enclosure, it must be mounted to agree 

with cover indication of operation. That is, when the cover indicates ON, the switch 

must be in the ON condition.

3. 

Before the cover is installed, the flat ground joint surface must be 

thoroughly wiped clean of any dirt, grit, or other foreign substances and a light thin 

coating of lubricant placed on the joint to prevent possible corrosion.

The joint between the box and the cover has been made accurately to .0015” to 

prevent the passage of this accuracy is destroyed.

4. 

ALL cover screws must be installed with at least five full threads engaged 

and must be securely tightened. All cover openings must be closed with a suitable 

cover.

5. 

Gaskets must not be added to these devices. Only gaskets designed for 

and permanently installed in these devices may be used.

6. 

In accordance with the hazardous location information specifying Class 

and Group listing marked on the device, sealing fittings must be added that will 

comply with requirements in the latest issue of the Canadian Electrical Code or 

National Electrical Code and any special requirements that are stated in the 

instruction sheet with the enclosure.