MAINTENANCE DATA
After installation, this enclosure should be inspected at regular intervals. A visual inspection should ascertain that all
cover bolts are still tight; that all conduit connections are intact and free of corrosion, and that the enclosure mounting
bolts are tight and in good condition.
If the enclosure must be opened for servicing, to check or replace internal devices and apparatus, the following
procedures should be followed:
Loosen cover bolts. Replace any corroded, bent or otherwise damaged bolts with new, factory authorized bolts obtained
from an authorized Larson Electronics distributor. Open enclosure. Do not use hammer, screwdriver or any prying tool to
open cover.
Inspect machined, flame joint flange surfaces. Surfaces must be smooth, free of nicks, scratches, dirt or any foreign
particle build-up that would prevent a proper seal. Should surface be damaged, contact factory. Never attempt to rework
surfaces by sanding, grinding, etc. Surfaces must seat fully against each other to provide a proper explosion-proof joint.
Inspect water exclusion gasket. If gasket is damaged, do not attempt field replacement or repair. Contact a factory
authorized representative for a replacement cover. The damaged gasket can be removed from the cover, and the cover
without gasket can be used until a replacement is obtained. The cover, without gasket, can be safely used in Class I & II
hazardous (classified) locations, however, the enclosure may not be rain-tight or hose-down resistant. Follow Installation
Instructions at
▲ on Page 1.
WARNING:
Before servicing the enclosure, be sure the electrical power is
OFF
.
Disconnect
the enclosure from
the primary power source and
lock-out
.