USE AND CARE

Unauthorized modification may impair the function and/or safety of this device and could affect the life of the equipment. 

Always check for damaged or worn out parts before using the device. Store it in a secure place out of the reach of 

children when not in use. Inspect for good working condition prior to storage and before re-use.

 

 

REPLACEMENT PARTS

The 

EXP-EL-CSS-250A-R1-NO

 is designed to provide years of reliable performance. Should the need for replacement 

parts arise, please contact Larson Electronics. 

THESE  INSTRUCTIONS  MAY  NOT  COVER  ALL  DETAILS  OR  VARIATIONS  OF  THIS  PRODUCT  FOR  YOUR  EQUIPMENT  OR  INSTALLATION 

REQUIREMENTS.  SHOULD  FURTHER  INFORMATION  NOT  COVERED  BY  THESE  INSTRUCTIONS  BE  REQUIRED,  PLEASE  CONTACT  LARSON 

ELECTRONICS BY EMAIL AT 

SALES@LARSONELECTRONICS.COM

 OR BY PHONE AT 1-800-369-6671 FOR FURTHER ASSISTANCE. 

PLEASE VISIT LARSONELECTRONICS.COM FOR 

WARRANTY

 AND 

RETURN

 INFORMATION.

TROUBLESHOOTING

1. Sensor is always tripped

A.

Switch has been overloaded and contacts are burned out. 

Check the output load, remembering to include

 

inrush or inductive loads (coils, motors, ballasts).

B.

The setpoint may be too low. 

Verify monitored circuit amps are less than the fixed

 

setpoint of the 

AC Current Switch.

2.

Sensor will not trip

A.

The setpoint may be too high. 

Verify monitored circuit amps are greater than the

 

fixed setpoint of the 

AC Current Switch

.

B. Split Core models: The core contact area may be dirty. 

Open the sensor and clean the contact area.

C. Monitored current is below fixed setpoint.

Loop the monitored wire several times through the

 

aperature until the “sensed” current rises above min-imum. Sensed 

Amps = (Actual Amps) x (Number of

 

Loops). Count loops on the Inside

 

of the aperature.

D. Switch has been overloaded and contacts are burned out. 

Check the output load, remembering to include

 

inrush on inductive loads (coils, motors, ballasts).

MAINTENANCE 

There are no serviceable parts inside the fixture. However, it is good practice to routinely clean and check the 

fixture for proper function. 