Chapter VII. Specification
Single Phase Input, Single Phase Output
Capacity
500VA
1kVA
2kVA
3kVA
5kVA
10kVA
15kVA
20kVA
Input
Voltage (Optional)
1 Phase 2 Wire: 110V/220V/230V/240 ± 10%
Frequency
50Hz or 60Hz ± 5%
Output
Voltage
0-150V (Low Voltage range)
0-300V (High Voltage range)
Frequency
40.0Hz to 120Hz (Higher than 120Hz is customized)
Current
Low-grade
4.2A
8.4A
16.8A
25A
41.6A
83.2A
125A
166.6A
High-grade
2.1A
4.2A
8.4A
12.5A
20.8A
41.6A
62.5A
83.3A
Load stabilization Rate
≤
±1%
Frequency Stability
≤
±0.01%
Harmonic Distortion
Pure Sine Wave
≤
2%
Frequency meter
4 digit, digital frequency meter, resolution 0.1Hz/Step
Voltmeter
4 digit, digital voltage meter, resolution 0.1V
Ammeter
4 digit, digital ammeter, resolution 0.1A
Watt meter
4 digit, digital Watt meter, resolution 0.1W
Protection
With overload, short circuit, over temperature
Instantaneous power failure protection and alarm device
Working Environment
Temperature
0 - 40 deg.
℃
Humidity
0 - 90% (Non condensation)
IND-SFC Series
Larson Electronics, LLC
Phone: (877) 348-9680
Fax: (903) 498-3364
www.larsonelectronics.com