WIRE INSTALLATION (cont.)

0.7 inch

(17.8mm)

<Table.2 / Tabla.2 / Tableau.2> 

Lug Information / Información de las zapatas / Information sur les cosses

Wire Binding Screw 

Torque /

Par de apriete del 

tornillo de sujeción de 

cables / 

Couple de la vis de 

fixation de fils

31.9 lb-in/ lbs-pulg/ lbpo 

(3.6 N

m)

39.9 lb-in/ lbs-pulg/ lbpo 

(4.5 N

m)

47.8 lb-in/ lbs-pulg/ lbpo 

(5.4 N

m)

55.7 lb-in/ lbs-pulg/ lbpo 

(6.3 N

m)

55.7 lb-in/ lbs-pulg/ lbpo 

(6.3 N

m)

Cu

1

14~10AWG

8AWG

6~3AWG

2~1AWG

2~1/0AWG

1

1

1

1

Cu

Cu / AI

Cu / AI

AI

AL100TE

15 ~100A

Strip Length / Sección sin 

alslamiento /

Longuer de denudage

Size/

Tamaño/

Calibre

Number per Lug /

Cantidad por

zapata /

Nombre par cosse

Conductor / Conductor / Conducteur

Type /

Tipo /

Type

Ampere

Range /

Gama en A /

Gamme (A)

Catalog

Number /

No. de catalogo /

N de catalogue

Lug /

Zapatas /

Cosses

1. Square conductor ends and perform conductors to final configuration. Using a proper insulation stripping tool, strip conductor

ends as recommended in Table 2. Do not nick strands.

2. If terminal mounter assemblies are not installed, install it (A).

3. Install cable in terminal mounter assemblies (B), and torque wire binding screw as recommended on the faceplate and Table 2

(C).

31.9, 39.9, 47.8, 55.7lb-

in /lbs-pulg / lb-po

(3.6, 4.5, 5.4, 6.3 N•m)

(UTE100 2P)

(UTE100 3P)

<Fig. 5> 

wire installation /

instalación de 

cable /installation de 

fil.

MPD-XX-CB-SF-489

 Series

 

Summary of Contents for MPD CB-SF-489 Series

Page 1: ...NG CODES RISK OF FIRE OR ELECTRIC SHOCK FIXTURE INSTALLATION REQUIRES KNOWLEDGE OF FIXTURE S ELECTRICAL SYSTEMS IF NOT QUALIFIED CONTACT A QUALIFIED ELECTRICIAN BE CERTAIN ELECTRICAL POWER IS OFF BEFO...

Page 2: ...eaker Mounting Bolt Drilling Plan Plan de perforaci n de tornillo de montaje del interruptor Plan de forage des Vis de montage du Disjoncteur Fig 3 Circuit Breaker Escutcheon Dimensions Dimensiones de...

Page 3: ...ion indicates a TRIP position and is between the ON and OFF positions See Fig 4 Circuit Breaker Reset After an automatic or accessory initiated trip or a manual PUSH TO TRIP operation the circuit brea...

Page 4: ...ngth Secci n sin alslamiento Longuer de denudage Size Tama o Calibre Number per Lug Cantidad por zapata Nombre par cosse Conductor Conductor Conducteur Type Tipo Type Ampere Range Gama en A Gamme A Ca...

Page 5: ...them B 3 Arrange wire through wire opening in auxiliary cover to avoid pinching wires 4 Replace auxiliary cover C and be careful not to pinch wires when installing cover Replace all auxiliary cover s...

Page 6: ...rical personnel 3 Turn off all power supplying this equipment before working on or inside equipment 4 Always use a properly rated voltage sensing device to confirm power is off 5 Replace all devices d...

Page 7: ...ding to rated current and function as follows Rated current In A FTU TU MCS UTE100 3P 100 UTE100 2P 100 Type of trip units Tipo de unidad de disparo Type de d clencheurs FTU Fixed thermal Fixed magnet...

Page 8: ...Type of trip units Tipo de unidad de disparo Type de d clencheurs 100A 40 C 2P Im 1000A 100A 40 C 3P Im 1000A 00 1 A 40 C 3P Im 1000A FMU Adjustable thermal Fixed magnetic T rmico ajustable magn tico...

Page 9: ...nside equipment 2 Remove circuit breaker in reverse order of installation TROUBLESHOOTING If problems occur during installation refer to the following guide If trouble persists contact Larson Electron...

Page 10: ...perate if the housing is cracked or damaged All fasteners should be properly seated USE AND CARE Unauthorized modification may impair the function and or safety of this device and could affect the lif...

Reviews: